10. Installation Instruction
10.1 Select the Best Location
10.1.1
Indoor Unit
•  There should not be any heat source or steam near the
unit.
•  There should not be any obstacles blocking the air
circulation.
•  A place where air circulation in the room is good.
•  A place where drainage can be easily done.
•  A place where noise prevention is taken into consideration.
•  Do not install the unit near the door way.
•  Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
•  Recommended installation height for indoor unit shall be
at least 2.5m.
10.1.2
Outdoor Unit
•  If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
•  There should not be any animal or plant which could be
affected by hot air discharged.
•  Keep the spaces indicated by arrows from wall, ceiling, fence
or other obstacles.
•  Do not place any obstacles which may cause a short circuit of
 the discharged air.
•  If piping length is over the rated length, additional refrigerant
should be added as shown in the table below:
Example: If the unit is installed at a 10m distance, the quantity of
additional refrigerant should be 50 g.
…… (10-7.5) m x 20g/m = 50 g
Piping size
Model
Gas Liquid
Rated
Length
(m)
Max
Elevation
(m)
Min Piping
Length (m)
Max
Piping
Length
(m)
Additional
Refrigerant
(g/m)
UE9HKE
3/8
” 1/4"
7.5
5
3
15
20
UE12HKE 3/8
” 1/4”
7.5
5
3
15
20
11.1.3 Indoor/Outdoor Unit