15. Troubleshooting 
Guide 
15.1  Refrigeration cycle system 
In order to diagnose malfunctions, ensure the air conditioner is free 
from electrical problems before inspecting the refrigeration cycle. 
Such problems include insufficient insulation, problem with the 
power source, malfunction of a compressor and a fan. The normal 
outlet air temperature and pressure of the refrigeration cycle 
depends on various conditions, the standard values for them are 
shown in the table to the right. 
 
 
 
 
Normal Pressure and Outlet Air Temperature (Standard)
 
Gas Pressure 
Mpa 
(kg/cm
2
G) 
Outlet air 
Temperature 
(°C) 
Cooling Mode
0.9 ~ 1.2 (9 ~ 12) 
15 ~ 17 
Heating Mode 2.3 ~ 2.8 (23 ~ 28) 
35 ~ 41 
Condition:  - Indoor fan speed = High 
                  - Outdoor temperature = 35°C at cooling mode 
                     and 7°C at heating mode. 
                  - Compressor operates at rated frequency 
Different in the intake 
and outlet 
air temperatures 
Normal 
Value of electric current 
during operation 
Dusty condenser 
preventing heat radiation
Excessive amount 
of refrigerant 
Gas Side 
pressure 
Inefficient compressor 
Insufficient refrigerant 
Clogged strainer or 
capillary cube 
•  Measuring the air 
temperature different 
•  Measuring electric current 
during operation 
•  Measuring gas side 
pressure 
More than 8°C 
(15 minutes after an 
operation is started) for 
cooling mode. 
Above 14°C  
(15 minutes after an 
operation is started) for 
heating mode. 
Less than 8°C at the cooling mode 
Less than 14°C at the heating mode
Higher than specified 
Heating 
Mode 
High 
Low 
Low 
Lower than specified 
Inefficient compressor 
Insufficient refrigerant 
Clogged strainer or 
capillary cube 
Cooling 
Mode 
Low 
Low 
Low