Riello Vision Dual 2200 VSD 2200 User Manual

Product codes
VSD 2200
Page of 4
mODElS
VSD 1100
VSD 1500
VSD 2200
VSD 2200 ER
VSD 3000
VSD 3000 ER
POwER
1100VA/990W
1500VA/1350W 2200VA/1980W 2200VA/1760W 3000VA/2700W 3000VA/2400W
INPUT
Nominal voltage
220-230-240 Vac
Voltage range without battery 
intervention
162 Vac < Vin < 290 Vac
Max allowable voltage
300 V
Nominal frequency
50 or 60 Hz ±5Hz
Frequency range
50 Hz ± 5% / 60 Hz ± 5%
Power factor
> 0.98
Current distortion
≤7%
OUTPUT
Voltage distortion with linear 
load / with non-linear load
< 3% / < 8% 
Frequency
Selectable: 50 Hz or 60 Hz or automatic selection
Waveform
Sinusoidal
Current crest factor
2.5 : 1
ECO Mode and 
Smart Active Output
98.5%
BATTERIES
Type
VRLA AGM lead acid maintenance free batteries
Charging time
2-4 hours
OVERlOAD TImES
100% < Load < 110%
5 minutes
110% < Load < 150%
10 seconds
Load > 150%
1 second
OTHER FEATURES
Net weight (kg)
16.5
17.5
28
15.5
31.5
16.5
Gross weight (kg)
20
21
33
20.5
36.5
21.5
Dimensions (hwd) (mm)
87x450x425 (2Ux19”x425)
87x450x625 (2Ux19”x625)
Packaging dimensions 
(hwd) (mm)
240x500x600
240x600x760
Surge protection
300 joule
Protection devices
Overcurrent - short-circuit - overvoltage - undervoltage - thermal - excessive low battery protection devices
Communication
USB / DB9 with RS232 and contacts / Slot for communications interface
Input sockets
1 IEC 320 C14
1 IEC 320 C20
Output socket
8 IEC 320 C13
8 iEC 320 C13 + 1 iEC 320 C19
Compliance with Standards
Safety: EN 62040-1 and Directive 2006/95/EL; EMC: EN 62040-2 category C2 and Directive 2004/108/EL
Ambient temperature
0°C / +40°C
Relative humidity
< 95% non-condensing
Colour
Black
Noise level
< 40 dBA @ 1 m
Standard equipment 
provided