Lapara LA-AVR-1200 User Manual
www.laparaups.com
LA-ITR-LCD
Technical Specifications
ITR-LCD SERIES – HIGH PERFORMANCE LINE-INTERACTIVE UPS
MODEL
LA-ITR-800
LCD
LA-ITR-1100
LCD
LA-ITR-1500
LCD
LA-ITR-2000
LCD
LA-ITR-2500
LCD
LA-ITR-3000
LCD
CAPACITY
800VA/640W 1100VA/880W 1500VA/1200W 2000VA/1600W 2500VA/2000W 3000VA/2400W
INPUT
Voltage
110/120VAC or 208/220/230/240VAC
Acceptable Voltage Range
81-145VAC / 162-290VAC
Frequency Range
60/50 Hz (auto sensing)
OUTPUT
Voltage regulation (AC Mode)
110/120VAC or 208/220/230/240VAC
Voltage regulation (Battery Mode)
±1%
Frequency Range (Battery Mode)
60 Hz or 50 Hz ±1 Hz
Current Crest Ratio
3:1
Harmonic Distortion
5% max. @ 100% linear load, 10% máx. @ 100% non-linear load (before alarm)
Transfer time
Typical 2-6 ms, 10ms max.
Waveform (Battery Mode)
Pure Sine Wave
BATTERY
Type
&
Number
12V/7AHx2 12V/9AHx2 12V/7AHx4 12V/9AHx4 12V/7AHx6 12V/9AHx6
Charging Volt.
27.4 VDC
±1% 54.8
VDC
±1%
82.1 VDC
±1%
Backup time
10 min.
10 min
13 min
13 min
14 min
12 min
Standard Model
Typical
Recharge time
Recharge time
4 hours recover to 90% capacity
Charging current
4A / 8A
4A / 8A
4A / 8A
Long-run Model
Charging Volt.
27.4
VDC
±1%
54.8
VDC
±1%
82.1
VDC
±1%
INDICATORS
LCD Display
AC mode, Battery mode, Load level, Battery level, Input Voltage, Output Voltage, Overload,
Fault and Low battery
PROTECTION
Full Protection
Overload, discharge and overcharge protection
ALARM
Battery Mode
Sounding every 10 seconds
Low Battery
Sounding every second
Overload
Sounding every 0,5 seconds
Fault
Continuously sounding
INTERFACE
Output connectors
8 x IEC
7 x IEC
Communication ports
1xUSB + 1xRS-232 + 1xRJ11
PHYSICAL
Dimensions,
DxWxH (mm)
DxWxH (mm)
380 x 438 x 88
480 x 438 x 88
600 x 438 x 88
Standard Model
Net Weight (Kg)
12.9
14.23 21.08 23.11 30.65 32.24
Dimensions,
DxWxH (mm)
DxWxH (mm)
380 x 438 x 88
480 x 438 x 88
600 x 438 x 88
Long-run Model
Net Weight (Kg)
10.8
14
18
ENVIRONMENT
Humidity
0-90 % RH @ 0 - 40°C (non condensing)
Noise Level
Less than 45dB
MANAGEMENT
RS-232 & USB
Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Specifications are subject to change without further notice
- 16 -