Technical Specifications
LA-ON-31 SERIES (3PHASE IN / 1PHASE OUT) ON-LINE UPS
MODEL
LA-ON31-10K
(L)**
LA-ON31-10K
ISO (L)**
LA-ON31-15K
(L)**
LA-ON31-20K
(L)**
LA-ON31-20K ISO
L**
CAPACITY
10KVA/8000W 10KVA/8000W 15KVA/12000W 20KVA/6000W 20KVA/16000W
INPUT
Low Line Transfer
176 VAC (phase voltage) ±3 @ 100% load
110 VAC (phase voltage) ±3 @ 50% load
Low Line Comeback
186 VAC (phase voltage) @ 100% load
120 VAC (phase voltage) @ 50% load
High line Transfer
300 VAC (phase voltage) ± 3%
Voltage
range
range
High line Comeback
290 VAC (phase voltage) ± 3%
Frequency Range
46~54Hz at 50Hz / 56~64Hz at 60Hz
Power Factor
≧ 0.99 @ 100% load
OUTPUT
Output Voltage
208/220/230/240
VAC
104/110/115/120
VAC or
208/220/230/240
VAC
208/220/230/240 VAC
104/110/115/120
VAC or
208/220/230/240
VAC
AC Volt. Regulation (Batt. mode)
± 1%
Frequency Range (Synchronized
Range)
Range)
46~54Hz at 50Hz / 56~64Hz at 60Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio
3:1
Harmonic Distorion
≦2% THD (Linear
Load)
≦5% THD (Non-
Linear Load)
≦2% THD (Linear
Load)
≦6% THD (Non-
Linear Load)
≦2% THD (Linear Load)
≦5% THD (Non-Linear Load)
≦2% THD (Linear
Load)
≦7% THD (Non-
Linear Load)
AC Mode to Batt.Mode
Zero
Transfer
time
time
Inverter to Bypass
Zero
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC
Mode
89% 85% 89% 89% 87%
Battery
Mode
86% 83% 88% 87% 83%
BATTERY
Battery type
12V / 9AH
Quantity
20 pcs. (18-20 pcs adjustable)*
20pcsx2strings (18-20pcs adjustable)*
Typical Recharge Time
9 hours recover to 90% capacity
Max Charging Current
1A
2A
N/A
Standard
Model
Model
Charging Voltage
273 VDC
±1%
Quantity
Depending on applications
Quantity 4A
8A
Long-run
model
model
Max Charging Current
273 VDC
±1%
INDICATORS
LCD Display
UPS status, Load level, Battery level, Input/Output voltage, Discharge time and Fault
ALARM
Battery mode
Battery mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
PHYSICAL
Dimensions DxWxH (mm)
592x250x576 592x250x826
815x250x826
Standard
Model
Net Weight (Kg)
83
144
164
N/A
Dimensions, DxWxH (mm)
592x250x576 592x250x826
592x250x576
815x250x826
Long-run
model
Net Weight (Kg)
28
91
40
144
ENVIRONMENT
Humidity
0-95% RH at 0 - 40°C (non-condensing)
Noise Level
< 58dB at 1 m
< 60 dB at 1 m
SOFTWARE MANAGEMENT
Smart RS-232 & USB
Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix & Mac
Optional SNMP
Power management from SNMP manager and web browser
*When using from 18-19 itnernal batteries, the unit will derate according to the following forumula: P = P
Rating
x (N/20 X 100%)
** L means Long-run model
Note 1: Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC
Note 2: If the UPS is installed or used in a place where the altitude is above 1000m, the output power must be derated 1% per 100m
Specifications are subject to change without further notice.
Note 1: Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC
Note 2: If the UPS is installed or used in a place where the altitude is above 1000m, the output power must be derated 1% per 100m
Specifications are subject to change without further notice.