Lapara LA-AVR-1200 User Manual
www.laparaups.com
LA-ON33
Technical specifications
LA-ON-33 SERIES (3PHASE IN / 3PHASE OUT) ON-LINE UPS
MODEL
LA-ON33-10K (L)**
LA-ON33-20K (L)**
CAPACITY
10KVA/8000W 20KVA/6000W
INPUT
Low Line Transfer
176 VAC (phase voltage) ±3 @ 100% load
110 VAC (phase voltage) ±3 @ 50% load
Low Line Comeback
186 VAC (phase voltage) @ 100% load
120 VAC (phase voltage) @ 50% load
High line Transfer
300 VAC (phase voltage) ± 3%
Voltage
range
range
High line Comeback
290 VAC (phase voltage) ± 3%
Frequency Range
46~54Hz at 50Hz / 56~64Hz at 60Hz
Power Factor
≧ 0.99 @ 100% load
OUTPUT
Output Voltage
3 x 400V (3 phase + N)
AC Volt. Regulation (Batt. mode)
± 1%
Frequency Range (Synchronized
Range)
Range)
46~54Hz at 50Hz / 56~64Hz at 60Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio
3:1 (max)
Harmonic Distorion
≦2% THD (Linear Load)
≦5% THD (Non-Linear Load)
AC Mode to Batt.Mode
Zero
Transfer time
Inverter to Bypass
Zero
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
89%
Battery Mode
86%
87%
BATTERY
Battery type
12V / 9AH
Quantity
20 pcs. (18-20 pcs adjustable)*
20pcs x 2strings (18-20pcs adjustable)*
Typical Recharge Time
9 hours recover to 90% capacity
Max Charging Current
1A
2A
Standard
Model
Model
Charging Voltage
273 VDC
±1%
Quantity
Depending on applications
Quantity 4A
8A
Long-run
model
model
Max Charging Current
273 VDC
±1%
INDICATORS
LCD Display
UPS status, Load level, Battery level, Input/Output voltage, Discharge time and Fault
ALARM
Battery mode
Battery mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
PHYSICAL
Dimensions DxWxH mm
592 x 250 x 575
815 x 250 x 826
Standard
Model
Model
Net Weight (Kg)
83
164
Dimensions, DxWxH mm
592 x 250 x 575
592 x 250 x 575
Long-run
model
model
Net Weight (Kg)
28
40
ENVIRONMENT
Humidity
0-95 % RH at 0- 40°C (non-condensing)
Noise Level
< 58dB at 1 m
< 60 dB at 1 m
SOFTWARE MANAGEMENT
Smart RS-232 & USB
Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix & Mac
Optional SNMP
Power management from SNMP manager and web browser
*When using from 18-19 itnernal batteries, the unit will derate according to the following forumula: P = P
Rating
x (N/20 X 100%)
** L means Long-run model