HP BLc7000 681840-B21 User Manual

Product codes
681840-B21
Page of 43
HP BladeSystem
c7000 Server Blade
Enclosure
Dimensions
Height
17.4 in (442 mm)
Width
17.6 in (447.04 mm)
Depth
32 in (813 mm)
Shipping Dimensions
Height
29.88 in (759 mm)
Width
23.88 in (607 mm)
Depth
39.88 in (1013 mm)
Single Phase Enclosure
Weight
Unboxed
192 lb (87 kg)
Shipping
235 lb (106.6 kg)
Three -Phase Enclosure
NA/JPN Weight
Unboxed
222 lb (100.7 kg)
Shipping
265 lb (120.2 kg)
Three-Phase Enclosure
International Weight
Unboxed
222 lb (100.7 kg)
Shipping
265 lb (120.2 kg)
DC Input Enclosure
Weight
Unboxed
151 lb (68.5 kg)
Shipping
194 lb (88 kg)
Max Enclosure Weight
(approximate)
Unboxed
450 lb (204 kg)
Shipping
493 lb (223.6 kg)
Temperature Range
Operating
50° to 95° F (10° to 35° C)
Non-Operating
-22° to 140° F (-30° to 60° C)
Relative Humidity
Operating
10 to 90% relative humidity (Rh), 28°C (82.4°F)
maximum wet bulb temperature, non-
condensing.
Non-Operating
5 to 95% relative humidity (Rh), 38.7°C
(101.7°F)maximum wet bulb temperature, non-
condensing.
NOTE: Operating temperature has an altitude derating of 1.8° F (1° C) per 1,000 ft (304.8 m). No direct
sunlight. Upper operating limit is 10,000 ft (3,048 m) or 70Kpa/10.1 psia. Upper non-operating limit is
30,000 ft (9,144 m) or 30.3 KPa/4.4 psia. Storage maximum humidity of 95% is based on a maximum
temperature of 113° F (45° C). Altitude maximum for storage is 70 KPa.
Power
Input Requirements -
Single Phase Model
Rated input frequency
50 to 60 Hz
2400W PSU
Rated input voltage
200 to 240 VAC
Rated input current
per power supply
13.9 A at 200 VAC
13.3 A at 208 VAC
12.6 A at 220 VAC
Rated input power
per power supply
2780 VA
Rated input Frequency
50 to 60 Hz
2650W PSU
Rated input voltage
200 to 240 VAC
Rated input current
per power supply
14.4 A at 200 VAC
13.8 A at 208 VAC
13.1 A at 220 VAC