SPECIFICATIONS
INPUT
Voltage Window
160-280 VAC
160-280 VAC
Frequency
45-65 Hz
45-65 Hz
Phase / Wire
Single Line + Neutral + Grd
Single Line + Neutral + Grd
Power Factor
up to 0.99
up to 0.99
Current THD (100% Linear)
< 6%
< 6%
OUTPUT
Voltage Window
220/230/240 VAC
220/230/240 VAC
Voltage Adjustment
Nominal +1-3% / -1-3%
Nominal +1-3% / -1-3%
Voltage Regulation
+/-2%
+/-2%
Capacity
6000VA / 5400W
10000VA / 9000W
Rated Power Factor
0.9
0.9
Wave Form
SINE WAVE
SINE WAVE
Frequency Regulation
+/- .2% (Free Running)
+/- .2% (Free Running)
Transfer Time
0ms
0ms
Crest Factor
3:1
3:1
Efficiency AC to AC 
95%
95%
DC Start
Yes
Yes
BATTERY
Type
Sealed Lead Acid Maintenance Free
Quantity
20 pcs
20 pcs
Voltage
240 VDC
240 VDC
Recharge Time (typical)
4 hours to 90%
5 hours to 90%
DISPLAY
Status on LCD                                                   Line, Back-up, ECO Mode. Bypass Supply, Battery Low, Disconnect Battery, Overload, 
Transferring with interruption & UPS Fault
Readings on LCD          
Input /Output Voltage, Input/Output Frequency, Load Percentage, 
Battery Voltage & Internal Temperature 
Self-Diagnostics                                        
Upon Power-ON, Front Panel Setting & Software Control, 24-HOUR Routine checking
ALARMS
Audible and Visual
Line Failure, Battery Low, Transfer to Bypass, System Fault Conditions
PROTECTION
Overload
Inverter Supply: 105% - 150% for 160 Seconds
Short Circuit Protection
Yes
Yes
Overheat
Yes
Yes
Battery Low
Alarm and Switch off
Alarm and Switch off
Heat Dissipation at full load
< 615W
< 1100W
PHYSICAL
Dimensions (WxDxH)
440x680x88* (2U)
440x680x132* (3U)
Input / Output Connection
Hardwired
Hardwired
Net Weight
24 KG
28 KG
QUALITY
Quality Assurance
ISO9001 Certified
ISO9001 Certified
Safety Standard
EN62040-1-1, UL1778
EN62040-1-1, UL1778
EMC Standard
EN62040-2, EN61000-3-2, EN61000-3-3, FCC Class A
Marks
CE, UL
CE, UL
The data and text contained within this brochure are for general information only and can not be deemed as definitive, specifications can change without notice.
* Batteries separate
®
Uninterruptible Power Solutions
BORRI ROTATION+
6kVA - 10kVA PARALLEL
ON LINE DOUBLE CONVERSION
BORRI LTD
Systems House
• 
Eckington Business Park
Rotherside Road
• 
Eckington
Sheffield 
• 
S21 4HL
Tel:
+44 01246 431431  
Fax: 
+44 01246 431444
Email:
sales@borri.co.uk   
Web:
www.borri.co.uk
BORRI S.p.A
Via 8 Marzo, 2
52010 Bibbiena (Arezzo)
Italy
Tel:
+39 0575 5351  
Fax: 
+39 0575 561438
Email:
info@borri.it   
Web:
www.borri.it
BORRI ROTATION+
TECHNICAL SPECIFICATIONS 
6kVA - 10kVA 
07/11 - Version 3
BORRI ROTA+_6-10KVA_6pp  24/7/11  17:56  Page 1