APC GALAXY 5000 G5USV040P005SAIO User Manual

Product codes
G5USV040P005SAIO
Page of 68
34001813EN/AF
 - Page 16
2. Installation
Required cable sizes for parallel UPS installations with an external bypass
  
Rated 
power of 
each UPS 
unit
Number of 
parallel 
UPS units
Total rated 
power of 
the UPS
Bypass AC 
input or 
load line 
current
Cable 
size
(1)
in mm
2
The table opposite is an example for an 
installation with up to four UPS units.
 For installations with redundant units, take 
into account only the number of units required 
to supply the loads (e.g. in a three-unit 
installation where one unit is redundant, only 
two units count in determining the input and 
load currents).
 This table is valid for 400 V input and load 
phase-to-phase voltages, at rated load with a 
power factor of 0.8. For voltages of 380 or 
415 V, multiply the current values by 1.05 or 
0.96 respectively and, if necessary, modify 
the cable sizes accordingly.
 The cable sizes in this table concern the bold 
sections in the diagram below.
(1) Cable sizes are determined for U1000 
R02V type copper conductors (for aluminium 
conductors, increase the size by 30%). Size 
calculations also take into account a voltage 
of 400 V and grouping of four cables.
20 kVA
2
3
4
40 kVA
60 kVA
80 kVA
58 A
87 A
116 A
16
35
50
30 kVA
2
3
4
60 kVA
90 kVA
120 kVA
80 A
129 A
172 A
25
50
70
40 kVA
2
3
4
80 kVA
120 kVA
160 kVA
116 A
174 A
232 A
35
70
120
60 kVA
2
3
4
120 kVA
180 kVA
240 kVA
174 A
261 A
348 A
70
150
185
80 kVA
2
3
4
160 kVA
240 kVA
320 kVA
232 A
348 A
464 A
120
185
2 x 120
100 kVA
2
3
4
200 kVA
300 kVA
400 kVA
288 A
432 A
576 A
150
2 x 95
2 x 150
120 kVA
2
3
4
240 kVA
360 kVA
480 kVA
348 A
522 A
696 A
185
2 x 150
2 x 185
  
Bypass AC
Normal AC
Bypass AC
GALAXY 5000
1
Normal AC
Bypass AC
GALAXY 5000
2
Normal AC
Bypass AC
GALAXY 5000
3
Load
External bypass