Bosch FCP‑500 FCP-O 500-P User Manual

Product codes
FCP-O 500-P
Page of 6
FCP‑500 Conventional Automatic Fire Detectors | 3
-
Other panels or their receiver modules with
identical connection conditions
-
UEZ 2000 LSN, BZ 500 LSN, FPA‑5000 and
FPA‑1200 via appropriate interfaces
The detectors and detector bases can be used
together with the „Rotaris” lamp by Philips.
The FCP‑OC 500, like the FCP‑O 500, is planned
according to the guidelines for optical detectors (see
DIN VDE 0833 Part 2 and VDS 2095).
The detectors must be installed exclusively in the
FCA‑500 bases provided. In addition, the detector
base must be installed in an FAA‑500‑BB ceiling mount
back box or in FAA‑500‑SB surface mount back box.
Note
For flush ceiling mounting with FAA‑500‑BB:
The false ceiling may have a maximum
thickness of
Note
32 mm. Above the false ceiling, a free height
of at least 110 mm is required.
FCP‑500 detectors are not intended for outdoor use.
A hemispherical space with a radius of 50 cm must
remain free below the detectors.
1
50 cm
2
3
1
Detector
2
Ceiling
3
hemispherical space below the detector
Care must be taken to ensure that neither people,
larger animals, plants nor any objects intrude into this
area and that no parts of the detector surface become
covered.
The detectors may only be installed in a position
which is out of arm's reach. We therefore recommend
a minimum installation height of 2.70 m.
The detectors may not be installed in rooms in which
data is transmitted by means of high-intensity infra-
red light (e. g. in rooms with IR systems for
interpreters).
The detectors must be mounted so that they are not
exposed to any direct sunlight.
A minimum distance of 50 cm from lamps must be
maintained. The detectors may not be mounted in a
cone of light from lamps.
The bases are equipped as standard with a spring
which is suitable for installation of the detector in
false ceilings. When the detector is installed in
concrete or wooden ceilings, these need to be
replaced by the stronger springs FAA‑500‑SPRING
with red markings.
Maximum permitted air speed: 20 m/s
Country-specific standards and guidelines must be
observed during the planning phase.
Technical Specifications
Parts Included
Detector type
Qty.
Components
FCP-O 500
1
Optical Smoke Detector, White
FCP-O 500-P
1
Optical Smoke Detector, Transparent with
Color Inserts
FCP-OC 500
1
Multisensor Detector Optical/Chemical,
White
FCP-OC 500-P
1
Multisensor Detector Optical/Chemical,
Transparent with Color Inserts
Technical Specifications
Electrical
Operating voltage
8.5 V DC bis 33 V DC
Standby current
FCA-500-EU
3 mA
FCA-500-E-EU
24 mA
Alarm current
47 mA
Fault current
FCA-500-EU
52 mA
FCA-500-E-EU
58 mA
Alarm resistance
0 Ω (UL application) or 680 Ω
Fault relay output
NC / C
Indicator output
Relay connects 0 V over 1.5 kΩ
Mechanics
Individual display
Two-color LED, 
red (alarm), green (test mode)
Dimensions
Detector
Ø 113 x 55 mm
Detector with trim ring
Ø 150 x 55 mm
Detector with cover, base and
ceiling mount back box
Ø 150 x 110 mm
Housing material
Polycarbonate
Housing color
Signal white, RAL 9003
Front plate color
FCP‑O 500/ FCP‑OC 500
Signal white matt
FCP‑O 500‑P/ FCP‑OC 500‑P Transparent/silver-gray
Weight
Without / with packaging
FCP-OC 500(-P)
180 g / 370 g
FCP-O 500(-P)
170 g / 360 g
Trim Ring
30 g / 60 g
www.boschsecurity.com