Socomec NETYS PR RT 3300VA NPR-3300-RT Leaflet

Product codes
NPR-3300-RT
Page of 2
13
Catalogue 2013
N T
Y
S PR 
from 1700 to 3300 VA - Rack/Tower
Single-phase UPS
Technical data
N TYS PR Rack/Tower
Sn
1700 VA
2200 VA
3300 VA
Pn
1350 W
1800 W
2700 W
Input / output
1/1
INPUT
Rated voltage
230 V
Voltage tolerance
161 V ±4% (selecting wide mode) -276 V ±4%
Rated frequency
50/60 Hz with automatic selection
Mains connection
IEC320-C14 (10 A)
IEC320-C20 (16 A)
OUTPUT
Automatic Voltage Regulation (AVR)
The AVR increases (boost 1) the output voltage by 14% 
when the input voltage drops below 90% of the nominal value.
The AVR decreases (bucks) the output voltage by 12% 
when the input voltage rises above 106% of the nominal value.
Rated voltage
230 V ±5%
Rated frequency
50/60 Hz ±0.1%
Wave form
Sine wave
Protection
Normal Mode: overload (110% for 3 minutes)
Battery Mode: overload (110% for 30 seconds); shortcircuit protected
Connections
8 (10 A) x IEC 320
8 (10 A) x IEC 320
1 (16 A) x IEC 320
BATTERIES
Type
Sealed lead-acid maintenance free - expected life 3/5 years
Back-up time 
(1)
6 min
8 min
6 min
COMMUNICATION
Interfaces
RS232 - USB
Ethernet adapter
NET VISION (TCP/IP & SNMP) optional card
Local communication software
Local View
Data line protection
NTP data line suppressor: RJ45 10 Base T
UPS CABINET
Dimensions W x D x H
440 x 436 x 87 mm
440 x 608 x 87 mm
Weight
18 kg
28.2 kg
31.5 kg
STANDARDS
Safety
EN 62040-1, AS 62040-1
EMC
EN 62040-2, AS 62040-2
Product certification
CE, C-Tick (N876)
(1) @ 75% of load.
Standard communication 
features
  LOCAL VIEW: ideal UPS monitoring and 
shutdown point-to-point solution for 
Windows
®
, Linux and Mac OS X
®
 operating 
systems.
  HID: UPS management based on Windows
®
 
and Mac OS X
®
 embedded service - USB 
interface.
  MODBUS/JBUS RTU (RS232).
Communication options
  NET VISION: professional WEB/SNMP 
interface for UPS monitoring and shutdown 
management of several operating systems.
  Dry-contact interface.
   Rails
Battery extensions
N TYS PR
+ 1 (NPR-B1700-RT) + 2 (NPR-B1700-RT)
1700 VA
22 min
42 min
N TYS PR
+ 1 (NPR-B3300-RT) + 2 (NPR-B3300-RT)
2200 VA
37 min
72 min
3300 VA
22 min
43 min
Connections
Control panel
1. Fan / air vents
2. EPO Emergency Power Off
3. USB serial port
4. RS232 serial port
5. Connector for external battery extension
6. UPS output sockets (2 segments)
7. NTP protections (RJ45)
8. Slot for optional communication boards
9. Input socket
10. UPS full power output socket
1. On / Off
2. Load present
3. Load level (5 steps)
4. General Alarm
5. Battery fault / Replace the battery
6. Overload
7. Battery capacity
8. Normal mode / Battery mode (flashing)
9. Automatic Voltage / Regulation active
10. Configuration
11. Programmable outlets
12. Input value
13. UPS test / Buzzer off
14. Navigator button
15. Enter
1700 VA
2200 VA
NET
y
S
 141 A
6
6
5
5
4
4
3
3
2
2
1
8
9
NET
y
S
 142 A
8
9
7
7
6
5
4
3
2
1
10
8
9
NET
y
S
 143 A
3300 VA
7
5
9
2
10
7
11
12
4
3
15
14
13
1
8
6
NET
y
S
 144 A