Socomec NET1500-PR-1U Leaflet
1. Slot for optional communication boards
2. Input protection
3. Network Transient Protector
4. Output sockets (IEC 320 10 A)
2. Input protection
3. Network Transient Protector
4. Output sockets (IEC 320 10 A)
5. Main input socket (IEC 320)
6. USB Port
7. RS232 serial port
8. DIP switches
6. USB Port
7. RS232 serial port
8. DIP switches
Single-phase
UPS
N
e
T
Y
S PR
from 1000 to 3000 VA
Connections
Communication software
•
UNI VISION software for the control
and automatic shutdown of applications
connected to Windows™ and Linux.
•
UNI VISION PRO software for the
manage ment of connected applications
and to control automatic shutdowns. Serial
cable included.
•
NET VISION interface SNMP / WEB
manager for the connection of the UPS to
the Ethernet network. This accessory can
be integrated in the UPS by means of the
slot located on the back panel.
•
BMS: possibility to integrate the UPS with
BMS (Building Management Systems) -
JBUS protocol.
•
HID: UPS management based on
Windows™ embedded service - USB
interface.
•
Warning relay interface: this is an optional
card (slot-mounted) that will manage 5
indication circuits with isolated contacts
carrying information on the status of the
UPS. The maximum voltage that can be
applied to the contacts is 240 VDC, and
the maximum current 1 A.
Relay contacts can be set individually
for NO (default) or NC operation, and
programmed selectively for customized
monitoring of the UPS.
Battery Hot-swap
Battery can be replaced from the front
without removing and disconnecting the
UPS.
MODeLS
N
e
T
Y
S PR
1000 Rack 1U
N
e
T
Y
S PR
1500 Rack 1U
ITeM CODe
NeT1000-Pr-1u
NeT1500-Pr-1u
UPS Power
1000 VA
(670 W)
1500 VA
(1000 W)
Input
230 V (default) ; 220 V, 230 V, 240 V selectable ; 50 / 60 Hz auto-sensing
Output
230 V (nominal) ; 50 / 60 Hz
Outut sockets
4 x IEC 320 (10 A)
Data line protection
NTP data line suppressor: RJ45 10 Base T
BATTerIeS
Type
sealed lead-acid maintenance free - expected life 3 / 5 years
Typical back-up time
(1)
12 minutes
COMMuNICATION
Communication interface
RS232 - USB
Ethernet
NET VISION (TCP / IP & SNMP) optional card
eNVIrONMeNT
Dimensions (WxDxH mm)
440 x 578 x 44,5
Weight
21 kg
23 kg
Reference standards
(EN) IEC62040-1-1 (safety), EN 62040-2 (EMC) , EN 61000-4-5 / C62.41:1991 (surge)
(1) Back-up time at 75 % of the nominal power.
Technical data
NET
y
S
091
A
NET
y
S
094
A
NET
y
S
096
A
NET
y
S
097
A
NET
y
S
095
A
Control panel
ON-OFF button
Load segment 1 (green)
Load segment 2 (green)
Service (red)
Battery mode (yellow)
Overload (red)
Power ON (green)
Test / Alarm
reset button
1
5
6
7 8
2
4
3
www.socomec.com
Non contractual document.
© 2010, Socomec SA. All rights reserved.
© 2010, Socomec SA. All rights reserved.
D
OC
125013
VALID FOR FRANCE
VALID FOR ITALY
ISO 9001:2008
FM 28237
ISO14001:2004
EMS 553476
Included
•
Mounting bracket for 19” rack
•
Adjustable rails
Mounting bracket
M3 x 6 bracket screws
Rear Hold-Down Bracket
Rear
Front
Assembly
Wing Nuts
Wing Nuts
Wing nut for rear
Hold-down bracket
Rail assembly