Emerson Liebert MPX PEM 230/400VAC 63A MPXPEM-EHBEXZ30 User Manual

Product codes
MPXPEM-EHBEXZ30
Page of 40
Liebert
®
 MPX
 Installation and Assembly
14
3.2
Liebert
®
 MPX
 System Assembly
3.2.1 Attach an MPX PEM
 or MPX BRM
 to the MPX PRC
Tools Required
• Tamper-resistant No. 1 Torx screwdriver bit, included with MPX PEM
• No. 1 PoziDriv screwdriver bit, included with MPX PEM
• No. 1 Phillips screwdriver, field-supplied
Before beginning to assemble the Liebert MPX:
• Ensure that utility power is not connected to any module or component.
• Ensure that no equipment is connected to the MPX BRM (Branch Receptacle Module).
• Ensure that the circuit breaker on the MPX BRM is Off.
After the MPX PRC (Power Rail Chassis) has been installed in the rack, it is ready for attachment of 
an MPX PEM (Power Entry Module) and then the MPX BRMs (Branch Receptacle Modules).
Emerson strongly recommends attaching the MPX PEM first, positioning it at either end of the MPX 
PRC. The module’s position will not adversely affect operation, but placing it at the end of the chassis 
will ease cable routing and separation of power and control cables in the rack.
Proper orientation of the MPX PRC is required to allow for the best use of the top or bottom entry into 
your rack. If cables will enter through the top of the rack, be sure that the MPX PRC has the power 
bus to the right side. This will put the MPX PEM in a position where the input cord will be closest to 
the top of the rack.
If cables will enter through the bottom of the rack, be sure that the MPX PRC is oriented so that the 
power bus is to the left side. This will put the MPX PEM in a position where the input cord will be 
closest to the bottom of the rack.
To balance the loads, be sure that the installed MPX BRMs have more than one unique line 
configuration (L1-L2, L2-L3, L3-L1, L1-N, L2-N, L3-N). This will help to ensure that none of the 
phases is overloaded.
If the MPX PEM is a Variable-Capacity model, an MPX IPC (input power cord) is required. Last, an 
optional Liebert RPC (rack PDU card) can be installed.
!
WARNING
Risk of arc flash and electric shock. Can cause equipment damage, injury or death.
This unit must be properly and securely installed on the MPX PRC (Power Rail Chassis). 
Emerson strongly recommends that the MPX PEM be installed only by an individual who has 
been properly trained and qualified to perform electrical work.
Connect only one MPX PEM (Power Entry Module) to an MPX PRC (Power Rail Chassis). 
Connecting more than one MPX PEM could cause cross-conduction. Cross-conduction can 
cause upstream overcurrent protective devices (OCPD) trip or the resulting short circuit 
current may exceed the OCPD A.I.C. ratings.
Whenever the MPX PEM is connected to power, the connectors on the bottom are energized 
with hazardous voltage. 
Connect input power only after: 
• the MPX PEM (Power Entry Module) is properly installed on the MPX PRC (Power Rail 
Chassis) 
• the  MPX  IPC
 (Input Power Cord) is properly connected to the MPX PEM
Connect input power to the Liebert MPX only while the MPX IPC is properly connected to the 
MPX PEM. Failure to do so may subject the user to hazardous voltages.