Page of 40
Liebert
®
 MPX
 System Modules
4
2.0
L
IEBERT®
 MPX
 S
YSTEM
 M
ODULES
2.1
MPX PRC
—Power Rail Chassis/Power and Communication Bus
The MPX PRC acts as the fundamental building block of the Liebert MPX. Power and 
Communications buses are integrated into the full length of the MPX PRC. The MPX BRM
 (Branch 
Receptacle Modules) and MPX PEM
 (Power Entry Module) lock onto the MPX PRC, adding power 
input, power output, monitoring and management, depending on the type of module.
The MPX PRC is available in two lengths:
The MPXPRC-V1880XXX will accommodate up to six standard size (266 mm) MPX BRMs (Branch 
Receptacle Modules); the MPXPRC-V1035XXX will accept up to three MPX BRMs. Each size of MPX 
PRC also accepts a single MPX PEM.
The MPX PRC has five power bus slots that allow the connection of the MPX PEM and MPX BRM 
modules to three phases of power, neutral and protective earth. A communication bus provides the 
path through which the Liebert RPC, MPX PEM and MPX BRM modules communicate. The MPX 
PRC also has a module connector slot that permits secure attachment of MPX PEM and MPX BRM 
modules via their integral connectors. Spacer covers are available to cap off unused sections of the 
MPX PRC’s surface. The spacer covers reserve positions to insert MPX BRMs for future expansion.
Part #
Length, mm (in)
Typical Cabinet Size
MPXPRC-V1880XXX
1880 (74.07)
42U
MPXPRC-V1035XXX
1035 (40.78)
23U
!
WARNING
Risk of connecting two MPX PEMs to one MPX PRC. Can cause equipment damage, injury or 
death.
Connect only one MPX PEM (Power Entry Module) to an MPX PRC (Power Rail Chassis). 
Connecting more than one MPX PEM could cause cross-conduction. A cross-conduction can 
cause upstream overcurrent protective devices (OCPD) trip or the resulting short circuit 
current may exceed the OCPD A.I.C. ratings.