Earthing
06/07
17
4.999.112.593
Earthing
The PABX Integral 5 easy must be earthed for safety reasons. 
Pertinent regulations: DIN EN 60950 "Safety of information technology systems" 
The Earthing and Potential Equalisation of the I5 System must comply with relevant national installation regulations.
For instance, for Germany: VDE 800 part 2, or also generally EN 50310.
Earthing is provided
either
using a separate earthing wire (green and yellow) from the potential equalization strip 
of the building to the earthing terminal of the BNx module. 
Make sure that: 
       The absolute minimum cross-section of the separately laid protective earths PE 
 
         is 2.5 mm
2
, if mechanical protection (e.g.: conductors sheathed in a cable, 
 
         in a cable duct or conduit),
       otherwise it must be 4 mm
2
 
or
by a lockable earthing plug (via the earthing wire of the wall socket) (special earthed 
plug with cable).