Brainboxes ED-516 User Manual

Page of 8
Connect, Configure, Control
ED-516 ETHERNET TO Digital IO 16 Inputs 
Ethernet to Digital In
ED-516
• 16 Digital Inputs 
• 0 to 30 Volt inputs ideal for dry/Volt free 
contacts or wet contacts 
• Ideal for inductive, capacitive & resistive loads
• Gateway Port for NuDAM/ADAM modules   
• -30
o
C to +80
o
C Temperature range
• +5V to +30V DC Input Power
ED-516
Digital Channels
Inputs
Input Channels
16 non-isolated input channels
NPN/PNP
One jumper configures all inputs as either pull up for NPN, active low, 
type sensors or pull down for PNP, active high, type sensors
Logic Level 0:
0V to +1V maximum
Logic Level 1:
+3.5V to +30V maximum
Latched Inputs:
Triggered by user programmable positive or negative edges, stays 
true until acknowledged
Counter Inputs:
User programmable- counts positive or negative transitions 0-65335
Dry/Volt free Contact Example