Bosch D292 User Manual

Page of 3
Modules
D275
End‑of‑line (EOL) supervision module
Remote
Annunciator
s
SMK-RA5
Remote annunciator
Mounting Considerations
Depending on local regulations, the bases can be
surface mounted using anchors, mollies, or wing nuts.
The bases can be directly mounted on single‑gang
switch boxes or mounted on four‑inch octagonal
electrical boxes using the supplied adaptor plate.
Notice
Ensure the volume of any electrical box used
accommodates the number and size of conductors
as specified by the National Electrical Code (NEC)
or any local regulations having jurisdiction.
EOL Supervision
Use a D293E Base for the last detector or use one
D275 module per detector loop. Use the EOL
resistor(s) specified by the control panel
manufacturer.
Parts included
Quant.
Component
1
D292 Four‑wire Detector Base
1
Adaptor plate (P/N: 18851)
1
Hardware pack
1
Literature pack
Technical specifications
Electrical
Current (alarm):
12 VDC: 52 mA 24 VDC: 54 mA
30 VDC: 70 mA maximum
Current (standby):
0.12 mA maximum
Voltage (standby):
10 VDC to 30 VDC
Mechanical
Dimensions (diameter):
6.375 in. (16.2 cm)
Outputs
Alarm:
One normally‑open (NO) relay rated for 0.5 A at
100 VDC for resistive loads
Ordering information
D292 Four‑wire Detector Base
Four‑wire detector base with smoke and heat detector
heads
Order number 
D292
Accessories
D275 Power Supervision Module
Line supervision device for four-wire fire detection
circuits
Order number 
D275
 
2 | D292 Four‑wire Detector Base