AEG PROTECT B. 750 6000003916 Leaflet

Product codes
6000003916
Page of 2
Protect B: technical specifications
Classification VI SS 211 acc. to IEC 62040-3  
B. 750 
B. 1000 
B. 1500 
B. 2000 
B. 3000
Type power 
750 VA 
1000 VA 
1500 VA 
2000 VA 
3000 VA
 
500 W 
700 W 
1050 W 
1340 W 
2100 W
UPS-input
 
 
 
 
Input voltage 
220 Vac / 230 Vac / 240 Vac
Input voltage range without battery mode 
161 / 184 – 276 Vac (adjustable)
Frequency (auto selection) 
50 Hz / 60 Hz ± 5 Hz (> 40 Hz generator operation)
Current consumption (max.)  
5 A  
8 A  
10 A  
10 A  
16 A
UPS-output
Rated output voltage / AVR-technology  
220 Vac / 230 Vac / 240 Vac
Rated output voltage in battery mode  
± 5 %
Frequency in battery mode  
50 Hz / 60 Hz ± 0.1 Hz
Output current (at 230 Vac)  
3.2 A  
4.3 A  
6.5 A  
8.7 A  
13.0 A
Transfer time at mains outage  
 
 
2 - 4 ms (typical), 6 ms max.
Voltage waveform  
 
 
Sinusoidal
Overload response at mains operation  
 
  110 % for 3 min / 150 % for 200 ms
Overheat and short-circuit protection  
Yes  
Yes  
Yes  
Yes  
Yes
Battery 
Type  
Sealed, maintenance free; hot swappable (from 1500 VA)
Rated voltage  
24 Vdc  
48 Vdc  
96 Vdc
Autonomy time at rated load 
5 min  
5 min  
5 min  
5 min  
5 min
 
-  
-                          Runtime extension with scalable ext. battery packs
Overload / deep discharge protection  
Yes  
Yes  
Yes  
Yes  
Yes
Recharge time (to 90% of rated capacity)  
3 h  
3 h  
3 h  
3 h  
3 h 
Communication
Interfaces  
USB and RS232 for status and measurement levels, Slot for enhanced communications 
 
(pot.-free contacts / SNMP), EPO port for emergency power off
 
Configuration panel for voltage preselection and setting of operating mode
Shutdown software (on CD)  
Included for all typical operating systems (e.g. Windows, Linux, Mac),
 
single licence CompuWatch with a 5 fold network licence
Failure indicators (acoustical / optical)  
Separate LED bar graphs for UPS load and battery capacity,
 
indicators for mains failure, overload, battery discharge, battery replace, failure
General data
Audible noise (1 m distance)  
< 45 dB(A)
Operating temperature range  
0° – 35°C
EMC immunity 
EN 50091-2, EN 61000-3-2, EN 61000-3-3
 
EN 61000-6-3 Class A
Data lines protection 
RJ11 (Phone, Fax, Modem) / RJ45 (Ethernet 10 Mbit/s / 100 Mbit/s)
Humidity  
0 - 90 % (non condensing)
Installation height  
Up to 1000 m, at nominal load
Number of outlets 
4 x IEC 320 C13 
6 x IEC 320 C13 
8 x IEC 320 C13
 
removable module 
1 x IEC 320 C19
Equipment colour 
Blackline
Size appr. W x H x D (mm) UPS unit 
                            235 x 88 x 383  
 217 x 88 x 414 
438 x 88 x 582
Size appr. W x H x D (mm) battery unit 
217 x 88 x 414 
438 x 88 x 582
Weight appr. (kg) UPS uni 
8.5 kg 
9.5 kg 
 6.5 kg 
31.5 kg
Weight appr. (kg) battery unit 
12 kg 
40.5 kg
Shipment 
Mains-cord, 2 load-cords IEC 320-10A, USB and RS232 communication cable, 
 
management software “CompuWatch“ (CD), user-manual
Certification 
CE
PERFECT IN FORM AND FUNCTION
AEG is a registered trademark used under license from AB Electrolux • Specifications are subject to change without notice • 11/2008
AEG Power Solutions Ltd. 
Units 1-2, 97-101 Peregrine Road 
Hainault, Ilford
Essex IG6 3XJ
United Kingdom
Tel.: +44 (0) 208 500 1211 
Fax: +44 (0) 208 500 9365