Bosch F220-135F User Manual

Page of 4
 
Fire Alarm Systems | F220 Heat Detectors
F220 Heat Detectors
 
www.boschsecurity.com
 
 
 
 
 
 
 
 
u
Two-wire or four-wire bases
u
50 ft (15.2 m) maximum spacing between detectors
u
Visible identification of model: F220‑135 = no ring,
F220‑135F = gray ring, F220‑190F = black ring
u
Tamper detection
u
Dual color LED
The F220 Heat Detectors include:
• F220‑135: An electronic rate-of-rise, fixed
temperature heat detector that initiates an alarm
when the ambient temperature exceeds +135°F
(+57°C) or when the ambient temperature increases
by +15°F (+8.3°C) or more in less than 1 minute
• F220‑135F: An electronic fixed temperature heat
detector that initiates an alarm when the ambient
temperature reaches +135°F (+57°C).
• F220‑190F: An electronic fixed temperature heat
detector that initiates an alarm when the ambient
temperature reaches +190°F (+88°C).
The detectors use low current electronic circuitry, so
they can connect to 12 VDC nominal or 24 VDC
nominal power source circuits. When mounted on the
appropriate F220‑B6 Series Mounting Base, the F220
Heat Detectors provide general property protection
from fire.
Notice
Heat detectors are not life safety devices.
Functions
Compatible Bases
Configure the detectors as either two-wire or four-wire
depending on the mounting base selected. These
detectors are compatible with any of the F220‑B6
bases:
• F220‑B6 12/24 VDC Two-wire Mounting Base
• F220‑B6R Standard 12/24 VDC Four-wire Mounting
Base
• F220‑B6RS 24 VDC Four-wire Mounting Base with
Sounder
• F220‑B6C 12/24 VDC Four-wire Mounting Base with
Auxiliary Form C Relay
• F220‑B6E 12/24 VDC Four-wire Power Supervision
Mounting Base
• F220‑B6PM 24 VDC Four-wire Addressable Master
Base
• F220‑B6PS 12/24 VDC Four-wire Addressable Base
Dual-color LED
To verify the detector has power and the heat
detection circuitry functions, a dual-color LED
indicator flashes green every 8 sec when operating
normally. It flashes once every 4 sec when a trouble
condition exists. The LED latches on red if an alarm