17
Catalogue 2013
N T
Y
S RT 
from 1100 to 11000 VA
Single-phase UPS
Technical data
N TYS RT 
Sn
1100 VA
1700 VA
2200 VA
3000 VA
5000 VA
7000 VA
9000 VA
11000 VA
Pn
800 W
1200 W
1600 W
2100 W
4500 W
5400 W
7200 W
9000 W
Architecture
online double conversion VFI with input PFC and automatic bypass
Parallel redundant function
-
-
-
-
1+1
1+1
1+1
1+1
INPUT
Voltage
230 V (1ph) 160~275 Vac; up to 130 Vac @70% load
230 V (1ph) 181~280 Vac up to 100 Vac @50% load
Frequency
50/60 Hz +/-10% (Auto-Selectable)
Power factor / THDi
>0.98 / <6%
>0.99 / <5%
OUTPUT
Voltage
230 V (1ph) selectable 200 / 208 / 220 / 240V - 50 or 60 Hz + /- 2 % (+/- 0.05 Hz in battery mode)
Efficiency
up to 91% online mode
up to 92% online mode
Overload capability
up to 105% continuously; 125% x 3 min; 150% x 30 sec
up to 105% continuously; 125% x 5 min; 150% x 30 sec
Output connections
6 x IEC 320-C13 
(10 A)
6 x IEC 320-C13 (10 A) + 1 x IEC 320-C20 (16 A)
terminals
BATTERY
Standard autonomy*
8
12
8
10
8
6
8
6
Voltage
24 Vdc
48 Vdc
48 Vdc
72 Vdc
192 Vdc
192 Vdc
240 Vdc
240 Vdc
Recharge time
< 6 hr to recover 90% capacity
< 6 hr to recover 90% capacity
COMMUNICATION
Mimic panel
LED
LCD 6 languages
RS232 MODBUS protocol
USB HID protocol
-
-
-
-
WEB/SNMP (Ethernet RJ45 port)
option 
option 
option 
option 
COMM slot
Dry contacts card
option 
option 
option 
option 
option 
option 
option 
option 
EPO input (RJ11 port)
Modem/ADSL surge protection
-
-
-
-
Parallel port
-
-
-
-
STANDARDS
Performance & topology 
EN 62040-3 (VFI-SS-111)
Safety /EMC
EN 62040-1 (TÜV-GS certified) EN 62040-2
Product certifications
CE, TÜV-GS, C-Tick
IP rating
IP20
ENVIRONMENT
Operating ambient temperature
from 0 °C to +40 °C (from 15 °C to 25 °C for best battery life)
Storage temperature range
from -15 °C to +50 °C (from 15 °C to 25 °C for best battery life)
Relative Humidity
0-90% non-condensing
Noise level (ISO 3746)
< 45 dB
< 55 dB
DIMENSIONS & WEIGHT
UPS size std (W x D x H)
88.7 x 332 x 440 mm 88.7x 430 x 440 mm 88.7 x 430 x 440 mm 88.7 x 608 x 440 mm 177.4 x 670 x 440 mm 177.4 x 670 x 440 mm 261.2 x 623 x440  mm 261.2 x 623 x 440 mm
 UPS size RACK
2U
2U
2U
2U
2U+2U
2U+2U
3U+3U
3U+3U
 UPS weight std 
13 kg
21 kg
22 kg
31 kg
15.5+40 kg
16+40 kg
19.5+66 kg
20+66 kg
 EBM module size (W x D x H) 88.7 x 332 x 440 mm 88.7x 430 x 440 mm 88.7x 430 x 440 mm 88.7 x 608 x 440 mm 88.7 x 608 x 440 mm
88.7 x 608 x 440
130.6 x 623 x 440 mm 130.6 x 623 x 440 mm
 EBM module RACK 
2U
2U
2U
2U
2U
2U
3U
3U
 EBM module weight
16 kg
29 kg
29 kg
43 kg
40 kg
40 kg
66 kg
66 kg
* @ 75% of nominal load. 
Standard electrical features
  Built-in backfeed protection.
  Protection against atmospheric phenomena 
(NTP) for telephone / ADSL modems.
  RJ11 connection for Emergency Power Off 
(EPO).
  Connection for battery extension modules.
  Port for parallel operation (5000-11000 VA).
Electrical options
  1+1 parallel module (5000-11000 VA).
  Manual bypass without interruption  
(5000-11000 VA).
  Battery extension modules.
Standard communication 
features
  LOCAL VIEW: ideal UPS monitoring and 
shutdown point-to-point solution for 
Windows
®
, Linux and Mac OS X
®
 operating 
systems.
  HID: UPS management based on Windows
®
 
and Mac OS X
®
 embedded service - USB 
interface (1100-3000 VA).
  MODBUS/JBUS RTU (RS232).
  RT-VISION: professional WEB/SNMP 
interface for UPS monitoring and shutdown 
management of several operating systems 
(5000-11000 VA).
Communication options
  RT-VISION: professional WEB/SNMP 
interface for UPS monitoring and shutdown 
management of several operating systems 
(1100-3000 VA).
  Dry-contact interface.