Eaton 5130 1750VA 2U PW5130I1750-XL2U User Manual
Product codes
PW5130I1750-XL2U
RACk/TOwER MOdEls
Catalogue Number
Rating (VA/Watts)
Input Connection
Output Receptacles
2
Dimensions H x W x D mm
Weight kg
Rack/Tower Models: 230V, 50/60 Hz
PW5130i1250-XL2U
1250/1150
IEC C14-10A
(8) IEC-C13-10A
87 (2U) x 441 x 509
24.3
PW5130i1750-XL2U
1750/1600
IEC C14-10A
(8) IEC-C13-10A
87 (2U) x 441 x 509
26.6
PW5130i2500-XL2UAU
2500/2250
IEC C20-16A
(1) IEC-C19 16A, (8) IEC-C13 10A
87 (2U) x 441 x 634
33.8
PW5130i3000-XL2UAU
3000/2700
IEC C20-16A
(1) IEC-C19 16A, (8) IEC-C13 10A
87 (2U) x 441 x 634
33.8
PW5130i3000-XL3UAU
3000/2700
IEC C20-16A
(1) IEC-C19 16A, (8) IEC-C13 10A
131 (3U) x 441 x 484
34.3
Rack/Tower Extended Battery Modules
PW5130N1750-EBM2U
NA
NA
NA
87 (2U) x 441 x 509
30.4
PW5130N3000-EBM2U
NA
NA
NA
87 (2U) x 441 x 634
41.7
PW5130N3000-EBM3U
NA
NA
NA
131 (3U) x 441 x 484
41.7
1. 230V models are adjustable to 150-294V range. 2. All models are equipped with (2) load segments (programmable outlets).
BATTERy BACkuP TIMEs (IN MINuTEs)*
Rack/Tower Models
Load (VA/Watts)
Internal batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
PW5130i1250-XL2U
125/115
119
430
741
1052
1363
313/288
32
150
267
384
502
625/575
15
58
100
143
185
938/863
6
42
77
113
148
1250/1150
5
29
54
79
104
PW5130i1750-XL2U
175/160
80
245
410
575
740
438/400
24
96
168
240
312
875/800
9
36
62
89
115
1313/1200
6
24
42
60
79
1750/1600
3
16
28
41
53
PW5130i2500-XL2UAU
250/225
77
300
410
780
1064
625/563
28
122
207
309
412
1250/1125
11
55
100
150
206
2153/1938
6
31
59
90
120
2500/2250
3
23
42
63
85
PW5130i3000-XL2UAU / PW5130i3000-XL3UAU
300/270
70
242
448
634
820
750/675
24
105
180
255
330
1500/1350
10
44
73
101
130
2250/2025
5
25
47
69
91
3000/2700
3
17
32
47
62
*Battery backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
7
LanSafe, Eaton, ePDU, Flex, PowerChain
Management, PowerTrust, Powerware,
PowerPass, X-Slot, and PowerVision are
trade names, trademarks, and/or service
marks of Eaton Corporation. All other trade-
marks are the property of their respective
owners.
© 2008 Eaton Corporation
All Rights Reserved
Printed in AUS 9135FXA
November 2008
Eaton Industries Pty. Ltd.
Electrical Group
Head Office:
10 Kent Road Mascot,
NSW 2020 Australia
1300 UPS UPS (1300 877 877)
www.powerware.com.au
www.powerware.com.au 1300 UPS UPS
(1300 877 877)