CAPACITIES AND SELECTION DATA
 
 
4-3 
 
4.1.  SYSTEM SELECTION PROCEDURE 
  
The following system procedure is giving a sample regarding unit selection system, indicating how to use all 
parameters showed in this chapter. 
 
4.1.1.  SELECTION UNIT FEATURES 
 
 
Considering the building distribution, the possible indoor 
unit  position  and  the  available  air  flow  distribution,  select 
the  unit  features  that  are  giving  the  best  efficiency  and 
comfort to each room. 
Decide  the  Outdoor  Unit  position  getting  easy  service 
maintenance and easy refrigerant pipe installation. 
 
 
Therefore,  the  maximum  indoor  unit  capacity  combined 
with outdoor unit should be carefully considered for correct 
indoor unit distribution at each building 
 
 
4.1.2.  SELECTION GUIDE 
 
 
The following guide giving the method for indoor and 
outdoor unit selection. 
  
Step 1: Determine the system requirements
 
 
Calculate the cooling capacity and heating capacity of 
each indoor unit according to the following conditions: 
 
 
Total Load for each room 
 
Room 
Item 
1+2+3 
Estimated 
Cooling Load 
kW 
2.75 
4.24 
5.35 
12.34 
Estimated 
Heating Load 
kW 
2.90 
4.60 
6.00 
13.50 
*Example 
 
Temperature Condition 
Cooling 
Heating 
Outdoor Air Inlet 
 
Dry Bulb:  35.0ºC 
Outdoor Air Inlet 
 
Dry Bulb: 7ºC 
 
Wet Bulb: 0ºC 
Indoor Air Inlet 
 
Dry Bulb:  27,0ºC 
 
Wet Bulb: 19.5ºC 
Indoor Air Inlet 
 
Dry Bulb: 20ºC 
*Example 
  
Step 2
Select Unit Capacity Performance 
 
  
The  unit  kW  is  selected  following  the  Cooling 
capacity  and  Heating  capacity  showed  in  the 
combination table. 
 
  
Step 3
Read Selected Capacity Performance 
 
   
The unit performance should be calculated 
considering the following correction factors: 
1.
 
Cooling and Heating piping length 
2.
 
Outdoor unit performance capacity 
3.
 
Indoor unit performance capacity for each room 
cooling load 
 
Kindly refer to the unit selection combination table for 
correct capacity performance.