Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
1-22
 
 
1.3.2 
ADDITIONAL FUNCTION VIA DIP-SWITCH SETTINGS 
A new DIP Swtich is available on the PWBs of the indoor unit that provide additional functions via the settings on the switches. 
 
Applicable Model 
DIP SW Label 
RAK-18/25/35PSPA 
DSW1 
RAK-25/35/50PXA 
DSW1 
RAK-18/25/35PPA 
DSW1 
RAK-50/60/70PPA 
SW501 
RAK-18/25/35/50PEA 
DSW1 
RAK-18/25/35/50QXA 
DSW1 
RAK-18/25/35/50QPA 
SW501 
RAF-25/35/50PXA 
DIP-SW 
RAF-25/35/50QXA 
DIP-SW 
RAF-25/35/50RPA 
DSW1 
RAD-25/35/50RPA 
SW501 
RAD-50/60/70PPA 
SW501 
RAI-25/35/50RPA 
SW501 
 
ON 
 
 
 
 
 
Air conditioner Indoor PWB 
 
 
OFF 
 
Pin 
No. 
Function 
Switch Position / Setting 
AUTO RESTART 
function 
OFF 
Enable 
ON 
Disable 
 
 
DRY CONTACT 
function 
OFF 
Disable 
ON 
Enable 
 
 
DRY CONTACT 
Logic Select 
OFF 
HI Input 
Active 
ON 
LO Input 
Active 
 
 
HEATING / 
COOLING ONLY 
MODE SELECT 
OFF 
NORMAL 
(HEAT 
AND 
COOL) 
OFF 
HEATING 
ONLY 
ON 
COOLING ONLY 
OFF 
ON 
OFF 
REMOCON ID 
SELECT 
OFF 
SELECT 
ID A 
ON 
SELECT ID 
 
 
 
A. Pin No. 1: Auto Restart Function 
The AUTO RESTART function can be enabled or disabled by setting Pin No. 1 on the DIP SWITCH above to the ON or OFF 
position accordingly. 
 
B. Pin No. 2 & 3: Dry Contact Function  
Please refer to this chapter section 1.3.3  DRY CONTACT APPLICATION (USING DIP SWITCH) for more details 
 
C. Pin No.4 & 5: Operation Mode Selection Lock (Heating/Cooling Only Mode Select)  
When this function is enabled, the operation mode could be locked to either Heating Only (Heating or Fan) or Cooling Only 
(Cooling, Fan or Dehumidifying) by setting the Pin No.  4 and 5 accordingly.  
LOCKED MODE 
REMARKS 
HEATING ONLY 
Unit will not enter into Cooling mode although cooling mode is selected using the remote controller. 
COOLING ONLY 
Unit will not enter into Heating mode although heating mode is selected using the remote controller. 
 
D. Pin No.6: Remocon ID Select (to prevent mutual interference of communication signal) 
This function is used for selecting the ID communication channel between the wireless remote controller and indoor unit. 
After setting the ID channel on the pin No. 6, the wireless remote controller also  *need* to be changed to corresponding  
same ID communication channel to ensure correct communication. 
Applicable models 
Reference for changing ID channel on the wireless remote controller 
RAK-18/25/35PPA 
Chapter 9.1.1.4   SETTING THE PREVENTION OF MUTUAL INTERFERENCE 
RAF-50RPA 
RAK-18/25/35/50PEA 
Chapter 9.1.3.2   SETTING THE PREVENTION OF MUTUAL INTERFERENCE 
 
Note: As for other models that do not
 
 utilize this Pin No.6 of this DIP Switch 
Please refer to Chapter 
9.1.1.4  SETTING THE PREVENTION OF MUTUAL INTERFERENCE
 for other applicable 
models below on how to change ID communication channel by using wireless weekly remote controller   
Applicable models 
RAK-18/25/35PSPA  RAK-18/25/35/50QXA RAF-25/35/50PXA  RAD-25/35/50RPA RAI-25/35/50RPA 
RAK-25/35/50PXA  RAK-18/25/35/50QPA RAF-25/35/50QXA RAD-50/60/70PPA  
RAK-50/60/70PPA   
RAF-25/35RPA 
 
 
 
Please  refer to Chapter 
9.1.2.2  SETTING THE PREVENTION OF MUTUAL INTERFERENCE
  for  other applicable 
models below on how to change ID communication channel by using wireless remote controller  :   
Applicable models 
RAK-18/25/35PSA  RAK-18/25/35PSAN 
DIP SW Label