CAPACITIES AND SELECTION DATA
 
 
4-289 
 
 
 
4.4.   CORRECTION FACTORS ACCORDING TO PIPING LENGTH 
 
 
Correction Factor for 
Cooling Capacity
 according to 
Piping Length 
 
 
The cooling capacity should be corrected according to the 
following formula: 
 
 
CCA = CC x F 
 
 
CCA: Actual Corrected Cooling Capacity 
 
 
 
(kcal/h) 
 
CC:  Cooling Capacity in the Performance 
 
 
 
Table (kcal/h) 
 
F:  
Correction Factor Based on the 
 
 
 
Equivalent Piping Length 
 
 
Correction Factor for 
Heating Capacity
 according to 
Piping Length 
 
 
The heating capacity should be corrected according to the 
following formula: 
 
 
HCA=  HC x F 
 
 
HCA: Actual Corrected Heating Capacity 
 
 
 
(kcal/h) 
 
HC:  Heating Capacity in the Performance 
 
 
 
Table (kcal/h) 
 
F:  
Correction Factor Based on the 
 
 
 
Equivalent Piping Length 
 
 
 
 
The correction factors are shown in the following figure. 
Equivalent Piping Length for: 
–  One 90º Elbow is 0.5m. 
–  One 180º Curve is 1.5m. 
 
 
 
 
 
 
H: 
Vertical Distance Between Indoor Unit and Outdoor 
Units in Meters   
 
L: 
Actual One-Way Piping Length Between Indoor Unit 
and Outdoor Unit in Meters 
 
EL: 
Equivalent Total Distance Between Indoor Unit and 
Outdoor Unit in Meters  
(Equivalent One-Way Piping Length)