CAPACITIES AND SELECTION DATA
4-307
4.6.6. RAM-70NP4A
Whichever indoor units are installed, cooling and heating capacity depends on how many and which indoor units are operating at
the same time.
the same time.
POSSIBLE
COMBINATIONS
TO OPERATE
COOLING
HEATING
TOTAL
(kW)
CAPACITY
RATING
(kW)
(RANGE)
OUTDOOR UNIT
EER Class
CAPACITY
RATING
(kW)
(RANGE)
OUTDOOR UNIT
COP
Class
TOTAL
INPUT
(W)
AMPERE (A)
TOTAL
INPUT
(W)
AMPERE (A)
TOTAL
220V 230V 240V
TOTAL
220V 230V 240V
ONE
UNI
T
1.2
1.2
1.20
1.20
370
1.7 1.6 1.6 3.24
A
1.80
1.80
560
2.6 2.5 2.4 3.21
C
(1.00-1.60)
(200-480)
(1.10-2.20)
(320-850)
1.8
1.8
1.80
1.80
450
2.1 2.0 1.9 4.00
A
2.50
2.50
850
3.9 3.7 3.6 2.94
D
(1.50-2.00)
(280-500)
(1.80-3.50)
(320-1130)
2.5
2.5
2.50
2.50
650
3.0
2.9 2.7 3.85
A
3.40
3.40
1130
5.2 5.0 4.8 3.01
D
(1.50-2.80)
(280-720)
(1.80-4.70)
(320-1480)
3.5
3.5
3.50
3.50
1030
4.7
4.5 4.3 3.40
A
4.30
4.30
1520
7.0 6.7 6.4 2.83
D
(1.50-3.90)
(280-1130)
(1.80-5.80)
(320-1950)
5.0
5.0
5.00
5.00
1640
7.5
7.2 6.9 3.05
B
6.50
6.50
2400
11.0 10.5 10.1 2.71
E
(1.50-5.60)
(280-1800)
(1.80-7.20)
(320-2530)
T
W
O
U
NIT
S
1.2+1.2
2.40
1.20+1.20
2.40
690
3.2 3.0 2.9 3.48
A
1.80+1.80
3.60
950
4.4 4.2 4.0 3.79
A
(1.50-2.80)
(380-980)
(2.20-4.70)
(200-1100)
1.2+1.8
3.00
1.20+1.80
3.00
920
4.2 4.0 3.9 3.26
A
1.80+2.50
4.30
1100
5.1 4.8 4.6 3.91
A
(1.50-3.50)
(380-1000)
(2.20-5.20)
(200-1300)
1.2+2.5
3.70
1.20+2.50
3.70
1030
4.7 4.5 4.3 3.59
A
1.80+3.40
5.20
1450
6.7 6.4 6.1 3.59
B
(1.50-4.00)
(380-1300)
(2.20-6.40)
(200-1780)
1.2+3.5
4.70
1.20+3.50
4.70
1390
6.4 6.1 5.9 3.38
A
1.80+4.30
6.10
1660
7.6 7.3 7.0 3.67
A
(1.50-5.20)
(380-1450)
(2.20-7.20)
(200-2010)
1.2+5.0
6.20
1.2+5.00
6.20
1850
8.5 8.1 7.8 3.35
A
1.80+6.50
8.30
2470
11.3 10.8 10.4 3.36
C
(1.50-5.90)
(380-2380)
(2.20-7.20)
(390-3120)
1.8+1.8
3.6
1.80+1.80
3.60
830
3.8 3.6 3.5 4.34
A
2.50+2.50
5.00
1380
6.3 6.1 5.8 3.62
A
(2.00-4.00)
(380-1020)
(2.20-6.40)
(390-2750)
1.8+2.5
4.3
1.8+2.5
4.30
1120
5.1 4.9 4.7 3.84
A
2.50+3.40
5.90
1680
7.7 7.4 7.1 3.51
B
(2.00-4.70)
(380-1360)
(2.20-7.20)
(390-3000)
1.8+3.5
5.3
1.8+3.5
5.30
1600
7.3 7.0 6.7 3.31
A
2.50+4.30
6.80
2030
9.3 8.9 8.5 3.35
C
(2.00-5.80)
(380-1950)
(2.20-7.20)
(390-3120)
1.8+5.0
6.8
1.8+5
6.80
2420
11.1 10.6 10.2 2.81
C
2.36+6.14
8.50
2470
11.3 10.8 10.4 3.44
B
(2.00-7.10)
(380-2820)
(2.20-9.50)
(390-3120)
2.5+2.5
5.0
2.50+2.50
5.00
1410
6.5 6.2 5.9 3.55
A
3.60+3.60
7.20
2070
9.5 9.1 8.7 3.48
B
(2.00-5.50)
(380-1720)
(2.20-9.50)
(390-3120)
2.5+3.5
6.0
2.50+3.50
6.00
1950
9.0 8.6 8.2 3.08
B
3.6+4.30
7.90
2420
11.1 10.6 10.2 3.26
C
(2.00-6.60)
(380-2380)
(2.20-9.50)
(390-3120)
2.5+5.0
7.5
2.33+4.67
7.00
2490
11.4 10.9 10.5 2.81
C
2.92+5.58
8.50
2470
11.3 10.8 10.4 3.44
B
(2.00-7.50)
(380-2980)
(2.20-9.50)
(390-3120)
3.5+3.5
7.0
3.5+3.5
7.00
2630
12.1 11.6 11.1 2.66
D
4.25+4.25
8.50
2640
12.1 11.6 11.1 3.22
C
(2.00-7.50)
(380-2940)
(2.20-9.50)
(390-3120)
3.5+5.0
8.5
2.88+4.12
7.00
2490
11.4 10.9 10.5 2.81
C
3.38+5.12
8.50
2470
11.3 10.8 10.4 3.44
B
(2.00-7.50)
(380-2890)
(2.20-9.50)
(390-3120)
5.0+5.0
10.0
3.50+3.50
7.00
2490
11.4 10.9 10.5 2.81
C
4.25+4.25
8.50
2470
11.3 10.8 10.4 3.44
B
(2.00-8.00)
(380-3170)
(2.20-9.50)
(390-3120)