Hitachi RAF-35RPA RAF35RPA User Manual
Product codes
RAF35RPA
GENERAL DATA
2-14
2.2.4. WALL TYPE (RAC-18WSAN/25WSAN/35WSAN)
OUTDOOR
UNIT
RAC-18WSAN
RAC-25WSAN
RAC-35WSAN
Minimum / Maximum indoor units
connectable
connectable
-
-
-
Minimum / Maximum connected
capacity
capacity
no
no
No
Nominal Cooling capacity (min - max)
kW
1.8 (*-*)
2.5 (*-*)
3.5 (*-*)
Nominal Heating capacity (min - max)
kW
2.3 (*-*)
3.2 (*-*)
4.0 (*-*)
Nominal cooling power input (min -
max)
max)
kW
0.30 (*-*)
0.47 (*-*)
0.81 (*-*)
Nominal heating power input (min -
max)
max)
kW
0.38 (*-*)
0.57 (*-*)
0.79 (*-*)
EER / COP
6.00/6.13
5.32/5.61
4.35/5.06
SEER / SCOP
-
-
-
Energy class (SEER/SCOP)
-
-
-
Noise level cooling (sound pressure)
dB(A)
46
48
49
Noise level heating (sound pressure)
dB(A)
46
48
49
Noise level (sound power)
dB(A)
60
62
63
Air flow (Cooling / Heating)
m
3
/h
1860 / 1620
1860 / 1620
1920 / 1620
Static pressure (nominal conditions,
maximum)
maximum)
Pa
-
-
-
Dimensions (H x W x D)
mm
600x792x299
600x792x299
600x792x299
Weight
kg
41
41
41
Colour (Munsell Code)
T-Beige (ZYY95)
T-Beige (ZYY95)
T-Beige (ZYY95)
Power supply
230V / 1Ph / 50Hz
230V / 1Ph / 50Hz
230V / 1Ph / 50Hz
Recommended fuse size
A
25
25
25
Starting current
A
TBC by June
TBC by June
TBC by June
Running current
A
1.89/2.27
2.81/3.37
4.63/4.54
Cable section
mm
2
3x1.50
3x1.50
3x1.50
Interconnection between indoor unit
and outdoor unit
and outdoor unit
mm
2
3x1.50
3x1.50
3x1.50
Piping diameter (Liq / Gas)
1/4” - 1/2”
1/4” - 1/2”
1/4” - 1/2”
Minimum piping length
m
5
5
5
Maximum piping length / height
difference
difference
m
20 / 10
20 / 10
20 / 10
Current quantity of refrigerant /
Chargeless
Chargeless
kg
1.4
1.4
1.4
Chargeless / Additional refrigerant
charge
charge
m / g/m
20/-
20/-
20/-
Working range (cooling / heating)
°C
-10~43/-20~21
-10~43/-20~21
-10~43/-20~21
Refrigerant
R410A
R410A
R410A
Condenser Fan
Propeller Fan
Compressor
Type
SCROLL
SCROLL
SCROLL
Oil Type
POE
POE
POE
Oil Charge
ml
380
380
380
Coil Resistance
1.21 at 20
C
1.21 at 20
C
1.21 at 20
C
1.47 at 75
C
1.47 at 75
C
1.47 at 75
C
Quantity
1
1
1
NOTE:
1. The Sound Pressure Level is based on the following conditions:
-
1 meter from the unit front surface and 1 meter from floor level
-
The above data was measured in an anechoic chamber. Please take into consideration reflected sound of your specific
site