Hitachi RAF-35RPA RAF35RPA User Manual
Product codes
RAF35RPA
GENERAL DATA
2-18
2.2.8. WALL TYPE (RAC-25WXA/35WXA/50WXA)
OUTDOOR
UNIT
RAC-25WXA
RAC-35WXA
RAC-50WXA
Minimum / Maximum indoor units
connectable
connectable
-
-
-
Minimum / Maximum connected
capacity
capacity
-
-
-
Nominal Cooling capacity (min - max)
kW
2.5(0.9-3.1)
3.5(0.9-4.0)
5.0 (0.9-5.2)
Nominal Heating capacity (min - max)
kW
3.4(0.9-4.4)
4.2(0.9-5.0)
6.3 (0.9-7.9)
Nominal cooling power input (min -
max)
max)
kW
0.58
(
0.25-1.29
)
0.92
(
0.25-1.30
)
1.555(0.155-2.200)
Nominal heating power input (min -
max)
max)
kW
0.79
(
0.25-1.25
)
1.01
(
0.25-1.30
)
1.745(0.155-2.200)
EER / COP
4.31/4.30
3.80/4.16
3.22/3.61
SEER / SCOP
5.8/4.3
5.9/4.3
6.0/4.2
Energy class (SEER/SCOP)
A+/A+
A+/A+
A+/A+
Noise level cooling (sound pressure)
dB(A)
46
47
50
Noise level heating (sound pressure)
dB(A)
47
49
52
Noise level (sound power)
dB(A)
60
61
65
Air flow (Cooling / Heating)
m
3
/h
1860 / 1620
1920 / 1620
1950 /1750
Static pressure (nominal conditions,
maximum)
maximum)
Pa
no
no
No
Dimensions (H x W x D)
mm
548×750×288
548×750×288
600x792x299
Weight
kg
31
35
42
Colour (Munsell Code)
T-Beige (ZYY95)
T-Beige (ZYY95)
T-Beige (ZYY95)
Power supply
230V / 1Ph / 50Hz
230V / 1Ph / 50Hz
230V / 1Ph / 50Hz
Recommended fuse size
A
15
15
16
Starting current
A
2.97/3.82
4.21/4.62
8
Running current
A
2.97/3.82
4.21/4.62
6.83/7.66
Cable section
mm
2
3x1.50
3x1.50
3x2.0
Interconnection between indoor unit
and outdoor unit
and outdoor unit
mm
2
2x0.75
2x0.75
2x2.0
Piping diameter (Liq / Gas)
1/4” - 3/8”
1/4” - 3/8”
1/4" / 1/2"
Minimum piping length
m
5
5
5
Maximum piping length / height
difference
difference
m
20 / 10
20 / 10
30 / 10
Current quantity of refrigerant /
Chargeless
Chargeless
kg
0.87
1.05
1.35
Chargeless / Additional refrigerant
charge
charge
m / g/m
20/-
20/-
20/-
Working range (cooling / heating)
°C
-10
℃—
43
℃
/-15
℃—
21
℃
-10
℃—
43
℃
/-15
℃—
21
℃
-10 ~ 43 / -15 ~ 21
Refrigerant
R410A
R410A
R410A
Condenser Fan
Propeller Fan
Compressor
Type
ROTARY
ROTARY
Scroll
Oil Type
FV50S
FV50S
FV50S
Oil Charge
ml
320
320
420
Coil Resistance
0.858 at 20
C
0.858 at 20
C
0.74 at 20
C
-
-
0.90 at 75
C
Quantity
1
1
1
NOTE:
1. The Sound Pressure Level is based on the following conditions:
-
1 meter from the unit front surface and 1 meter from floor level
The above data was measured in an anechoic chamber. Please take into consideration reflected sound of your
specific site
specific site