GENERAL DATA 
2-20
 
 
2.2.10.  WALL TYPE (RAC-18WPA/25WPA/35WPA) 
OUTDOOR 
UNIT 
RAC-18WPA 
RAC-25WPA 
RAC-35WPA 
Minimum / Maximum indoor units 
connectable 
 
Minimum / Maximum connected 
capacity 
  
Nominal Cooling capacity (min - max) 
kW 
2.00 (0.90 - 2.50) 
2.50 (0.90 - 3.10) 
3.50 (0.90- 4.00) 
Nominal Heating capacity (min - max) 
kW 
2.50 (0.90 - 3.20) 
3.40 (0.90- 4.40) 
4.20 (0.90- 5.00) 
Nominal cooling power input (min - 
max) 
kW 
0.55 (0.25 - 1.01) 
0.70 (0.25 - 1.29) 
1.090 (0.25 - 1.46) 
Nominal heating power input (min - 
max) 
kW 
0.58 (0.25 - 0.97) 
0.88 (0.25 -  1.25) 
1.100(0.25 -  1.70) 
EER / COP 
 
3.64/4.31 
3.57/3.86 
3.21/3.82 
SEER / SCOP 
 
5.8/4.2 
5.8/4.2 
5.9/4.3 
Energy class (SEER/SCOP)   
 
A+/A+ 
A+/A+ 
A+/A+ 
Noise level cooling (sound pressure)   
dB(A) 
46 
48 
49 
Noise level heating (sound pressure)   
dB(A) 
47 
49 
50 
Noise level (sound power) 
dB(A) 
60 
62 
63 
Air flow (Cooling / Heating)   
m
3
/h 
1860 / 1620 
1860 / 1620 
1920 / 1620 
Static pressure (nominal conditions, 
maximum) 
Pa 
Dimensions (H x W x D) 
mm 
505x700x258 
505x700x258 
548×750×288 
Weight 
kg 
27.0 
27.0 
36.0 
Colour (Munsell Code) 
 
Beige (5Y 7/2) 
Power supply 
 
230V / 1Ph / 50Hz 
230V / 1Ph / 50Hz 
230V / 1Ph / 50Hz 
Recommended fuse size 
15 
15 
15 
Starting current 
5.0 
5.0 
5.0 
Running current 
2.65/2.84 
3.58/4.25 
5.00/5.03 
Cable section  
mm
2
 
3x1.50 
3x1.50 
3x1.50 
Interconnection between indoor unit 
and outdoor unit 
mm
2
 
2x0.75 
2x0.75 
2x0.75 
Piping diameter (Liq / Gas) 
  
1/4” - 3/8” 
1/4” - 3/8” 
1/4” - 3/8” 
Minimum piping length 
5.0 
5.0 
5.0 
Maximum piping length / height 
difference 
20 / 10 
20 / 10 
20 / 10 
Current quantity of refrigerant / 
Chargeless  
kg 
0.82 
0.82 
1.00 
Chargeless / Additional refrigerant 
charge 
m / g/m 
20/- 
20/- 
20/- 
Working range (cooling / heating) 
°C 
-10
—43
-15
—21
 
-10
—43
-15
—21
 
-10
—43
-15
—21
 
Refrigerant 
 
R410A 
R410A 
R410A 
Condenser Fan 
 
Propeller Fan 
Compressor 
Type 
 
ROTARY 
ROTARY 
ROTARY 
Oil Type 
 
α68HES-H 
α68HES-H 
α68HES-H 
Oil Charge 
ml 
320±20 
320±20 
320±20 
Coil Resistance 
 
0.75 at 25
0.75 at 25
0.75 at 25
Quantity 
 
 
NOTE: 
1.  The Sound Pressure Level is based on the following conditions:  
1 meter from the unit front surface and 1 meter from floor level  
The above data was measured in an anechoic chamber. Please take into consideration reflected sound of your specific 
site