REMOTE CONTROLLERS OPERATION
 
 
 
9.1.1.1 
AUTOMATIC OPERATION  
COOLING/HEATING mode is decided by the room temperature. 
 
A.
 
COOLING/HEATING mode is decided during the 
initial start up
 of Automatic Operation 
Initial start up of Automatic Operation means the following either condition: 
 
Unit start up in Automatic Operation 
 
Automatic Operation mode is pressed while the unit is running in manual mode  
Start up room temperature 
COOL / HEAT 
>= Remote controller setting temperature 
Unit runs in COOLING mode 
< Remote controller setting temperature 
Unit runs in HEATING mode 
 
B.
 
COOLING/HEATING mode is decided 
in intervals after the initial start up
 of Automatic Operation (also known as 
Auto Changeover function) 
*Auto changeover function is not applicable to RAD-50PPA, RAD-60PPA, and RAD-70PPA models and to other indoor 
models when connected to Multizone outdoor unit. 
 
RAK-QXA, RAK-QPA, RAI-RPA, RAD-RPA, RAF-PXA, RAF-QXA, RAK-50PPA, RAK-60PPA, RAK-70PPA, RAK-50PXA
 
Intervals 
Duration 
1
st
 interval 
10 minutes 
2
nd
 interval 
15 minutes 
Subsequent interval 
Every 55 minutes 
 
RAK-PSPA, RAK-18PPA, RAK-25PPA, RAK-35PPA, RAK-25PXA, RAK-35PXA 
 
Intervals 
Duration 
1
st
 interval 
5 minutes 
2
nd
 interval 
15 minutes 
Subsequent interval 
Every 55 minutes 
 
RAF-RPA
 
Intervals 
Duration 
1
st
 interval 
30 minutes 
2
nd
 interval 
50 minutes 
Subsequent interval 
Every 55 minutes 
 
COOLING/HEATING mode is determined by setting the hysteresis on the final preset temperature. 
 
(RAK-QXA, RAK-QPA, RAI-RPA, RAD-RPA, RAF-PXA, RAK-50PPA, RAK-60PPA, RAK-70PPA, RAK-50PXA)
 
Final preset temperature
 = Remote Controller setting temperature + 
Σ
(sum of all types shift values) 
(e.g. temperature shift value, Powerful shift value, Eco shift value, Eco sleep shift value, etc) 
Current operation mode 
Current room temperature 
Next operation mode 
COOLING 
<=  [Final preset temperature - 3
 o
C
 
Change to HEATING 
COOLING 
>    [Final preset temperature - 3
 o
C
 
Continue COOLING 
 
Current operation mode 
Current room temperature 
Next operation mode 
HEATING 
>=  [Final preset temperature + 2
 o
C
 
Change to COOLING 
HEATING 
<    [Final preset temperature + 2
 o
C
 
Continue HEATING 
 
 
 
 
RAK-PSPA, RAK-18PPA, RAK-25PPA, RAK-35PPA, RAK-25PXA, RAK-35PXA, RAF-RPA 
 
Current operation mode 
Current room temperature 
Next operation mode 
COOLING 
<=  [Final preset temperature - 2
 o
C
 
Change to HEATING 
COOLING 
>    [Final preset temperature - 2
 o
C
 
Continue COOLING 
 
Current operation mode 
Current room temperature 
Next operation mode 
HEATING 
>=  [Final preset temperature + 3
 o
C
 
Change to COOLING 
HEATING 
<    [Final preset temperature + 3
 o
C
 
Continue HEATING 
 
 
 
 
Final preset 
temperature 
-3
o
C  
+2
o
Heating 
Cooling 
Final preset 
temperature 
-2
o
C  
+3
o
Heating 
Cooling