REMOTE CONTROLLERS OPERATION
9.1.1.1
AUTOMATIC OPERATION
COOLING/HEATING mode is decided by the room temperature.
A.
COOLING/HEATING mode is decided during the
initial start up
of Automatic Operation
Initial start up of Automatic Operation means the following either condition:
Unit start up in Automatic Operation
Automatic Operation mode is pressed while the unit is running in manual mode
Start up room temperature
COOL / HEAT
>= Remote controller setting temperature
Unit runs in COOLING mode
< Remote controller setting temperature
Unit runs in HEATING mode
B.
COOLING/HEATING mode is decided
in intervals after the initial start up
of Automatic Operation (also known as
Auto Changeover function)
*Auto changeover function is not applicable to RAD-50PPA, RAD-60PPA, and RAD-70PPA models and to other indoor
models when connected to Multizone outdoor unit.
RAK-QXA, RAK-QPA, RAI-RPA, RAD-RPA, RAF-PXA, RAF-QXA, RAK-50PPA, RAK-60PPA, RAK-70PPA, RAK-50PXA
Intervals
Duration
1
st
interval
10 minutes
2
nd
interval
15 minutes
Subsequent interval
Every 55 minutes
RAK-PSPA, RAK-18PPA, RAK-25PPA, RAK-35PPA, RAK-25PXA, RAK-35PXA
Intervals
Duration
1
st
interval
5 minutes
2
nd
interval
15 minutes
Subsequent interval
Every 55 minutes
RAF-RPA
Intervals
Duration
1
st
interval
30 minutes
2
nd
interval
50 minutes
Subsequent interval
Every 55 minutes
COOLING/HEATING mode is determined by setting the hysteresis on the final preset temperature.
(RAK-QXA, RAK-QPA, RAI-RPA, RAD-RPA, RAF-PXA, RAK-50PPA, RAK-60PPA, RAK-70PPA, RAK-50PXA)
Final preset temperature
= Remote Controller setting temperature +
Σ
(sum of all types shift values)
(e.g. temperature shift value, Powerful shift value, Eco shift value, Eco sleep shift value, etc)
Current operation mode
Current room temperature
Next operation mode
COOLING
<= [Final preset temperature - 3
o
C
]
Change to HEATING
COOLING
> [Final preset temperature - 3
o
C
]
Continue COOLING
Current operation mode
Current room temperature
Next operation mode
HEATING
>= [Final preset temperature + 2
o
C
]
Change to COOLING
HEATING
< [Final preset temperature + 2
o
C
]
Continue HEATING
RAK-PSPA, RAK-18PPA, RAK-25PPA, RAK-35PPA, RAK-25PXA, RAK-35PXA, RAF-RPA
Current operation mode
Current room temperature
Next operation mode
COOLING
<= [Final preset temperature - 2
o
C
]
Change to HEATING
COOLING
> [Final preset temperature - 2
o
C
]
Continue COOLING
Current operation mode
Current room temperature
Next operation mode
HEATING
>= [Final preset temperature + 3
o
C
]
Change to COOLING
HEATING
< [Final preset temperature + 3
o
C
]
Continue HEATING
Final preset
temperature
-3
o
C
+2
o
C
Heating
Cooling
Final preset
temperature
-2
o
C
+3
o
C
Heating
Cooling