REMOTE CONTROLLERS OPERATION
 
 
9-11 
 
9.1.2.1 
AUTOMATIC OPERATION  
COOLING/HEATING/DEHUMIDIFICATION mode is decided by the room temperature and external air temperature. 
 
A.
 
COOLING/HEATING/ DEHUMIDIFICATION mode is decided during the 
initial start up
 of Automatic Operation 
Initial start up of Automatic Operation means the following either condition: 
 
Unit start up in Automatic Operation 
 
Automatic Operation mode is pressed while the unit is running in manual mode  
 
Mode 
Room Temperature 
 
External Air Temperature 
*Temperature on 
remote controller will 
automatically set at 
Unit runs in COOLING 
mode 
Room temperature          
> 27˚C 
AND 
21˚C <=  External air 
temperature 
27˚C (Fan speed mode 
: AUTO, LOW, 
SILENT) 
OR 
Room temperature 
<=27˚C 
AND 
External air temperature 
>=25˚C 
Unit runs in 
DEHUMIDIFICATION 
mode 
Room temperature         
> 27˚C 
18˚C <=  External air 
temperatu
re <=21˚C 
Room temperature at 
the start of the 
operation (Fan speed 
mode: AUTO, LOW, 
SILENT) 
OR 
23˚C< Room temperature 
<=27˚C 
  
25˚C <=  External air 
temperature <=18˚C 
OR 
Room temperature 
<=23˚C 
AND 
21˚C <=  External air 
temperature <=25˚C 
Unit runs in HEATING 
mode 
Room temperature         
> 23˚C 
External air temperature 
<=18˚C 
23˚C (Fan speed 
mode: AUTO, LOW, 
MEDIUM) 
OR 
Room temperature 
<=23˚C 
AND 
External air temperature 
<=21˚C 
NOTE: *Please refer item C for the information on adjusting room temperature. 
 
 
 
 
B.
 
COOLING/HEATING/  DEHUMIDIFICATION  mode  is 
decided 
in  intervals  after  the  initial  start  up
  of 
Automatic  Operation  (also  known  as  Auto  Changeover 
function).  
 
Intervals 
Duration 
Every Interval 
60 minutes 
 
 
C.
 
ADJUST THE ROOM TEMPERATURE by pressing the (ROOM TEMPERATURE) button. 
 
Every time the button is pressed, a short beep sound is emitted and the temperature will change by 1
˚C. 
 
+1 is displayed if the temperature is set higher that the automatically set room temperature by 1
˚C. 
 
-1 is displayed if the temperature is set higher that the automatically set room temperature by 1
˚C. The adjustable 
temperature range is not higher or lower that 3
˚C of the automatically set room temperature.  
 
Humidity setting cannot be adjusted.