REMOTE CONTROLLERS OPERATION
 
 
9-17 
 
9.2.2. 
SHIFT VALUE 
1.
 
Press and hold 
 (START/STOP) button and 
 (ON TIMER) button at the same time until remote controller 
now enter ‘Shift value change mode’. 
2.
 
Press 
(START/STOP) button so that the display indicates 
 (FAN) speed. 
3.
 
Select 
(FAN SPEED) button to choose Heating Shift or Cooling Shift Mode. 
 
By setting fan speed to HIGH 
or MED
 , it will go to Cooling Shift mode. 
By setting fan speed to LOW 
 or SILENT
, it will go to Heating Shift mode.  
 
4.
 
Press 
 
(ROOM TEMPERATURE) button to change the shift value (-3
C ~ 0 ~ 3
C). 
 
5.
 
Press 
 
(START/STOP) button to send new shift value setting mode, the display indicate in stand by mode. 
 
 
NOTE:  
1.
 
There are total of 7 shift values ranging from -3 to 3. 
2.
 
The changed shift value will remain unchanged after turned off the power. 
 
9.2.3. 
ERROR CODE INFORMATION 
 
1.
 
In case failure occurs to the air conditioner, the error code will constantly appear on the wired remote controller 
display. 
 
 
TIMER 
LAMP 
BLINKING 
LED301 
BLINKING 
CODE 
MEANING 
INDO
O
R
 
 
 
 
 
 
Normal 
1 time 
 
 
 
 
 
 
Refrigerant cycle fault 
2 times 
 
 
 
 
 
 
Outdoor unit is under forced operation 
3 times 
9 times 
 
 
 
 
 
Communication error between indoor and outdoor 
units 
6 times 
 
 
 
 
 
Abnormal water level: ceiling/small duct 
9 times 
 
 
 
 
 
Indoor thermistor 
10 times 
 
 
 
 
 
Abnormal rotating numbers 
13 times 
 
 
 
 
 
IC401 data reading error 
00
 
 
01
 
 
02
 
 
03
 
 
06
 
 
09
 
 
10
 
 
13