Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
10-20
 
 
 
 CAUTION  
• 
Since 2-way outlet shown below cause performance 
problem, do not set it. 
 
Blower cover installation 
Install the blower cover only to the air outlet direction which 
is not in use. 
Install the blower cover at the diffuser shown. Fix the 
blower cover securely. 
 
 
Corner seal installation 
Install the corner seal at position shown. Fix the corner seal 
securely. 
Shall be installed regardless to 2 directions, 3 directions or 4 
directions. 
 
 
Selecting the Air flow switch 
1.  Turn power off. 
2.  Remover cover of the electrical box 
3.  When selecting discharge direction of 2 directions or 
3 directions, select the “AIR FLOW SELECTION” on 
the main PWB to 3 way. 
When selecting discharge direction to 4 directions, 
select the “AIR FLOW SELECTION” on the switch 
PWB to NORMAL. 
 
 
NOTE
During 2 directions or 3 directions, sound level will increase. 
Selecting the Air flow switch 
1.  Turn power off. 
2.  Remover cover of the electrical box 
3.  When install the indoor unit 2500mm or more form 
the floor, select the “STATIC PRESSURE SW” on 
the main PWB to HIGH PRESSURE 
When install the indoor unit below than 2500mm 
from floor, select the “STATIC PRESSURE SW” on 
the main PWB to NORMAL 
4 directions 
Pipe 
600mm or more 
600mm or more 
3 directions 
3 directions 
600mm or more 
1000mm or more 
2 directions 
2 directions 
60
0mm o
r mo
re
 
Pipe 
Pipe 
2 direction sample 
Fit the 
blower cover 
Blower cover  
A-A Section view 
 
Corner seal  
Corner 
seal 
 
Corner 
seal
 
Blower cover 
 
3 WAYS 
NORMAL 
A
IR
FLO
SEL
EC
T