Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
10-26
 
 
 
• 
In case of steel frame 
 
 
4.  Preparation for installing indoor unit 
• 
Remove 1 screw by which electric box is installed, 
and then remove electric box 
• 
Turn removed electric box with lead wires kept 
connected so that wire lead out section is 
positioned at the upper side, and hook the claw of 
electric box to side plate. Then fix the electric box 
to the bottom of the indoor unit using 1 screw. 
• 
Install 4 suspension clamps at both sides of indoor 
unit, 2 clamps at each side, using 8 tapping 
screws. (Since size of left and right clamps are 
different for certain parts, refer to diagram on the 
bottom) 
• 
Chamber of discharge of unit side (optional  part: 
RAU-DU2) on the indoor unit using 10 tapping 
screws. 
 
 
• 
Install bottom plates 1 and 2 on the bottom of the 
indoor unit using 9 tapping screws. (install bottom 
plate 1 first, followed by plate 2) 
• 
Cut and open dotted line section for suction port 
at the back of the indoor unit, using nippers (2 
locations) 
• 
Remove 2 screws at top plate end of indoor unit 
and chamber of suction of unit side using 7 
screws. 
 
150~160mm 
Insert 
(100~150kg) 
Concrete 
Reinforcing 
bar 
Suspension bolt 
(M10) 
Hanger bolt 
Angle 
About 130 
Suspension bolt 
(M10) 
Ceiling 
Bend slip-preventive metal 
C type metal 
Long nut 
Suspension 
bolt (M10) 
H beam 
Right side 
suspension clamp(2) 
Left side 
suspension clamp(2) 
Screw 
Screw 
Electric box 
Be sure to 
hook upper 
side claw to 
side plate 
21
 
33
 
Screw 
Indoor unit 
Chamber of discharge of 
unit side 
Remove the screw 
Top plate 
Screws to 
fit electric 
box 
Chamber of suction of unit side 
Indoor unit 
Screw 
Filter 
Filter holders 
Back plate 
(1) Bottom side suction opening 
Indoor unit 
Back plate 
(2) Back side suction opening 
Suspension 
bolt (M10)