Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
10-28
 
 
 
• 
Chamber of discharge grille 
Side view 
 
FRONT VIEW 
 
SIDE VIEW 
 
PLANE VIEW 
4.  Installation of suspension bolt 
• 
This is the same as for discharge/suction duct 
type. Follow instructions for discharge/suction duct 
type 
4.  Preparation for installing indoor unit 
• 
Remove 1 screw by which electric box is installed, 
and then remove electric box 
• 
Turn removed electric box with lead wires kept 
connected so that wire lead out section is 
positioned at the upper side, and hook the claw of 
electric box to side plate. Then fix the electric box 
to the bottom of the indoor unit using 1 screw. 
• 
Install 4 suspension clamps at both sides of indoor 
unit, 2 clamps at each side, using 8 tapping 
screws. (Since size of left and right clamps are 
different for certain parts, refer to diagram on the 
bottom) 
• 
Chamber of discharge of unit side on the indoor 
unit using 10 tapping screws. 
 
 
• 
Install bottom plates 1 and 2 on the bottom of the 
indoor unit using 9 tapping screws. (install bottom 
plate 1 first, followed by plate 2) 
• 
Cut and open dotted line section for suction port 
at the back of the indoor unit, using nippers (2 
locations) 
• 
Remove 2 screws at top plate end of indoor unit 
and chamber of suction of unit side using 7 
screws. 
 
 
Above 200 
Suspension bolt 
(
M10: Local purchase) 
54 
207 
400 
347 
28 
186
 
206
 
58
 
274
 
740 
310 
199 
Reinforcement 
Above 300 
Above 300 
860 
47
 
98
 
Suspension bolt 
(M10: local 
purchase
Ceiling 
Above 200 
110 
270
 
47
 
178
 
Opening on ceiling 
740 
53 
53 
48
 
96
 
Suspension 
bolt position 
740 
Right side 
suspension clamp (2
Left side 
suspension 
clamp (2) 
Electric box 
Be sure to hook 
upper side claw 
to side plate 
Screw 
Screw 
33
 
Screw 
Indoor unit 
Chamber of discharge of 
unit side 
Remove the screw 
Top plate 
Screws 
to fit 
electric 
box 
Chamber of suction of unit side 
Screw 
21
 
A
b
o
ve 330