10-36
 
 
• 
In case of wooden frame 
 
 
 
• 
In case of steel frame 
 
 
3.  Installation of the Indoor Unit 
a)  Mark the positions of the sling bolts, refrigerant 
piping connections and drain connection. 
b)  Ceiling work: If basically varies according to the 
building structure. Consult with the architect or 
interior finish worker for more information on this. 
i) 
To maintain the appropriate levelness of the 
ceiling and preventing from the vibration, the 
additional reinforcement in the ground of 
ceiling (building frame) is essential. 
ii) 
Provide a space for the air inlet grille, air 
outlet grille and maintenance work 
iii)  Do not suspend bolts on the indoor units. If 
connected, the light may flicker or the light 
unit may be rattled by vibration of the indoor 
units. 
c)  Mounting and Hanging the Indoor unit  
Field Supplied parts 
Sling Bolts 4-M10 or W3/8 
Nut  8-M10 or W3/8 
 
 
i) 
Put the nuts on each of the four hanging bolts 
 
d)  Hanging the Indoor Unit 
i) 
Hook the suspension bracket to the nut and 
washer of each hanging bolt, as shown 
starting at the opposite side to service cover 
side. 
ii) 
After checking that the nut and washer are 
correctly fixed by the retainers of the 
suspension bracket, hook the suspension 
bracket of the service cover side to the nut 
and washer. (Put the sling bolts away from 
the unit when hooking.) 
iii)  Piping and wiring work will be required in the 
ceiling after hanging the unit. Therefore, 
determine the drawing direction of pipe after 
piping and wiring work should be carried out 
up to the connecting positions before hanging 
the unit. 
 
e)  For reasons of the disaster prevention, the 
distance between under the roof and wall surface 
should be followed as shown in the figure below. 
• 
Use a non-flammable material for the duct. 
60~90mm square piece of lumber 
Nut 
Angle 
Angle 
Nut 
Suspension bolt 
Ceiling 
About 130 
(M10) 
Suspension bolt (M10) 
Insert 980~1470N  
(100~150kgf) 
150~160mm 
Reinforcing bar 
Concrete 
Suspension bolt 
Hanger bolt 
Angle 
About 130 
(M10) 
Ceiling 
Bend slip-preventive metal 
C type metal 
Long nut 
Suspension bolt 
(M10) 
H beam 
Suspension bolt 
(M10) 
(Unit: mm) 
Sling Bolts (4-M10 or W3/8 
(Field-supplied) 
Nut & Washer  
(4-M10 or W3/8) 
Nut (Field-supplied) 
Washer (Accessory) 
Unit 
False Ceiling Side 
Suspension 
Bracket 
Indoor Unit 
Retaining Nut 
Washer 
Washer 
Nut 
A
ppr
ox
 5
Sling Bolt 
Right side 
(Service Cover side) 
Left side 
Suspension 
Bracket 
Nut & 
Washer 
Suspension Bracket