Connect the motor connector of discharge duct to 
the connector CN8 (see diagram below) 
• 
Attach connector of this panel of the connector 
CN11A on the control PWB> 
 
10.  Setting of external static-pressure switch 
• 
Remove lid of electric box and set the “STATIC 
PRESSURE” switch. 
 
HIGH       : 80Pa 
NORMAL : 50Pa 
LOW        : 30Pa 
• 
If not set to HIGH STATIC-PRESSURE, there will 
be reduction of cooling and heating capacities. (At 
the time of delivery, the switch is set to “NORMAL”) 
11.  When connecting the H-Link 
• 
When connecting to H-link, a separately purchased 
RAC adaptor is required. 
• 
To install the wiring, the electrical box cover must 
be opened. 
• 
Connect the RAC adaptor to CN1101. 
• 
The connection cord and power cables are to be 
arranged and tied up as per the diagram as shown 
below. 
• 
Please refer to the respective user manuals of the 
RAC adaptor, for further details. 
 
12.  Protection of lead wire 
• 
Wrap aluminum tape around PVC tube between 
electric box and indoor unit (cord band). 
 
13.  Operation test 
• 
Please ensure that the air conditioners in normal 
operating condition during the operation test. 
• 
Explain to your customer the proper operation 
procedures as described in the user manual. 
• 
If the indoor unit does not operate, check to see that 
the connections are correct. 
 CAUTION 
• 
Trial run should be conducted on one unit at a time 
to check for incorrect wiring of connecting cord. 