Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
12-4
 
 
 
4)  Test run method 
• 
Turn power on 
• 
Remove lid of electric box and set the drain pump 
test run switch to TEST RUN 
• 
After checking the drainage, return the switch to 
NORMAL 
 
5)  Perform test running of drain pump to check drainage 
operation 
Caution 
If drain pump test run is always set to TEST, drain pump 
may malfunction 
12.4.3  CHECKING OF DRAWING HOSE 
①Connect the separate drain hose to the drain hose that is 
attached to the indoor unit 
②For keeping the smooth flowing of condensed water, the 
drain hose should be inclined as shown in figure below. 
 
 
Caution 
• 
Please ensure the smooth flow of condensed water of 
the indoor unit during installation. (Carelessness may 
result in water leakage 
• 
Be sure that the hose is not loosely connected or bent 
• 
In case drain piping cannot be done smoothly due to 
obstacles, it can also be arranged outside of the main 
unit as shown in the drawing below. 
• 
Maximum drain-up length shall be  
Applicable models 
Max drain up 
length 
RAD-25RPA/35RPA/50RPA 
300mm 
RAD-50PPA/60PPA/70PPA 
500mm 
 
• 
When the relative humidity of inlet or ambient air 
exceeds 80%, apply an (field-supplied) auxillary drain 
pan beneath the indoor unit as show below 
 
 
 
Suspension bracket 
(Field supplied) 
90° Elbow Pipe (VP25) 
(Field supplied) 
Lift piping for Drain-up 
(PVC Tube, VP25) (Field 
supplied) 
90° Elbow Pipe (VP25) 
(Field supplied) 
Indoor unit 
Drain pump 
Drain 
pan 
Drain piping (PVC Tube) 
Field supplied 
1/25 to 1/100 
down slope 
Hose clamp 
(235) 
188
 
(M
ax)
 37
4 t
o
 50
0 (
Dr
ain
-u
p l
e
n
g
th)
 
Indoor unit 
Auxiliary Drain Pan 
(Field-supplied) 
To the Atmosphere 
Pump of oil stove 
Water 
Pail 
Water pan 
Drain pump 
Drain pump test drive switch 
Normal 
Test 
Good 
Refrigerating 
pipes 
Drain 
hose 
Bad 
Bad 
Drain 
hose 
Condensed 
water pond 
Air pocket 
Bad 
Bad 
Ditch 
Condensed 
water pond