13-8
 
 
13.3.2 ELECTRICAL WIRING FOR INDOOR UNIT 
WARNING: 
– 
The appliance must be earthed 
– 
Remove the front panel and electrical cover to expose 
the electrical box in the indoor unit. 
– 
Insert the connecting cord from the bottom of the unit. 
– 
Fix the wire firmly to the terminal. 
• 
Applicable models : 
RAK-18PSA/RAK-25PSA/RAK-35PSA 
RAK-18PSAN/RAK-25PSAN/RAK-35PSAN 
 
Remove the terminal cover and screw , hold the upper 
part when removing. Then remove the lower cover. 
 
Connect the connecting cord with and fix with cord 
band 
• 
Applicable models : 
RAK-25PXA/RAK-35PXA/RAK-50PXA 
 
 
Pull the cover ① and ②in the directions as shown by  
arrows to remove the cover. 
 
• 
Applicable Models : 
RAF-25PXA/RAF-35PXA/RAF-50PXA 
 
 
WARNING: 
– 
Leave some space in the connecting cord for 
maintenance purpose and be sure to secure it with the 
cord band. 
– 
Secure the connecting cord along the coated part of 
the wire using the cord band. Do not exert pressure on 
the wire as this may cause overheating of fire 
 
Connection of connecting cord 
 
 
After remove the screw and cover , and 
put the connecting cords and fix the 
cover with screw 
 
Connect the 
earth cord 
 
Connect the 
earth cord 
After remove the screw 
and cover, and put the 
connecting cords and fix 
the cover with screws 
Securely screw in the connecting 
cord so that it will not get loose or 
disconnect. 
Tightening torque reference value: 
1.2 ~ 1.6Nm (12~16kgf.cm) 
Excessive tightening may damage 
the interior of the cord requiring 
replacement 
Connecting cord 
Terminal cover 
Screw 
Connecting Cord 
Cord Band 
Lower cover