Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
GENERAL DATA 
 
2-29 
 
2.2.19.  DUCT TYPE (RAD-50PPA/60PPA/70PPA) 
INDOOR 
Unit 
RAD-50PPA 
RAD-60PPA 
RAD-70PPA 
Nominal capacity adjustable  
  
Nominal Cooling capacity (min - max) 
kW 
5.0 (0.9-6.0) 
6.0 (0.9-7.0) 
7.1 (0.9-8.0) 
Cooling sensible capacity  
kW 
4.0 
4.5 
5.1 
Nominal Heating capacity (min - max) 
kW 
6.0 (0.9-7.0) 
7.3 (0.9-8.0) 
8.0 (0.9-9.0) 
Noise level cooling (sound pressure) 
(SL / L / M / H) 
dB(A) 
28/30/32/34 
28/30/32/34 
28/30/32/35 
Noise level heating (sound pressure) 
(SL / L / M / H) 
dB(A) 
29/31/33/35 
29/31/33/35 
29/31/33/36 
Noise level (sound power) 
dB(A) 
60 
60 
61 
Air flow cooling mode (SL / L / M / H) 
m
3
/h 
618/660/780/900 
618/660/780/900 
618/660/780/960 
Air flow heating mode (SL / L / M / H)  
m
3
/h 
618/660/780/900 
618/660/780/900 
618/660/780/960 
Fan Motor 
56 
56 
56 
Drain pump pressure lift 
cm 
Static pressure (SL / L / M / H) 
(nominal conditions SP 00) 
Pa 
-/30/50/80 
-/30/50/80 
-/30/50/80 
Dehumidification 
l/h 
2.8 
2.8 
5.2 
Included drain pump 
 
yes 
yes 
yes 
Max. height available for drain pump 
(RAD/RAI only) 
 
500 
500 
500 
Dimensions (H x W x D) 
mm 
270x900x720 
270x900x720 
270x900x720 
Panel dimensions (H x W x D) 
mm 
Weight 
kg 
35.0 
35.0 
35.0 
Colour (Munsell Code) 
 
Condensate Drain 
mm 
φ16 
φ16 
φ16 
Panel weight 
kg 
Panel reference 
 
Color of the panel (RAL) 
 
Running current 
6.4~5.9/7.3~6.7 
8.55~7.90/9.75~9.0 
11.6~10.7 / 10.7~9.8 
Power supply 
 
35V DC & 230V , 1Ph , 
50Hz from outdoor unit 
35V DC & 230V , 1Ph , 
50Hz from outdoor unit 
35V DC & 230V , 1Ph , 
50Hz from outdoor unit 
Cable section 
mm² 
N/A 
N/A 
N/A 
Piping diameter (Liq / Gas) 
  
1/4" / 1/2" 
1/4" / 1/2" 
1/4" / 5/8" 
Drain diameter (ext) 
mm 
φ16 
φ16 
φ16 
Remote control (optional only)  * 
 
SPX-RCDA/SPX-RCKA  SPX-RCDA/SPX-RCKA
 
SPX-RCDA/SPX-RCKA
 
Filter 
 
 
 
 
ACL Filter 
 
Dimensions (H x W x D) 
mm 
Pre-filter (Standard / Optional) 
 
Washable/- 
Washable/-
 
Washable/-
 
*
more information regarding remote control can be found in Chapter 9
*
 
NOTE: 
1.  The nominal cooling and heating capacity is the 
combined capacity of the HITACHI standard split 
system, and are based on the ISO 5151.
 
 
2.  The Sound Pressure Level is based on the following 
conditions:  
1.5  meter beneath the Unit 
The above data was measured in an anechoic 
chamber. Please take into consideration reflected 
sound of your specific site
 
 
Operation Conditions 
Cooling 
Heating 
 
Indoor Air Inlet Temperature
 
dB 
27.0 °C
 
20.0 °C 
 
WB 
19.0 °C
 
 
 
Outdoor Air Inlet 
Temperature
 
dB 
35.0 °C
 
7.0 °C
 
 
WB 
 
6.0 °C 
 
Piping Length: 5.0 meters; Piping Lift: 0 meter 
dB: Dry Bulb; WB: Wet Bulb