Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
14-6
 
 
14.1.7  MONO SPLIT RAK-18/25/35PPA / RAC-18/25/35WPA , RAK-18/25/35/50PEA / RAC-18/25/35/50WEA , 
RAF-25/35RPA / RAC-25/35FPA 
Warning 
Remember that voltage of 175V is applied to the 0V line on the 
P.W.B. or the like as shown in the diagram below 
Warning 
When using an oscilloscope, never ground it. Don’t forget 
that high voltage as noted in the left figure may apply to the 
oscilloscope. 
 
 
 
 
14.1.8  MONO SPLIT RAK-50/60/70PPA / RAC-50/60/70WPA 
Warning 
Remember that voltage of 175V is applied to the 0V line on the 
P.W.B. or the like as shown in the diagram below 
Warning 
When using an oscilloscope, never ground it. Don’t forget 
that high voltage as noted in the left figure may apply to the 
oscilloscope. 
 
 
 
 
Indoor controller 
Power 
Switch 
Voltage at point 
Power 
inlet 
Control 
P.W.B
  
Grounding 
Main P.W.B 
Outdoor controller 
DC35V 
0V 
0V Line 
Point 
Point 
Compressor 
motor 
I.P
.M
Point  (0V line) 
Ground voltage 
175V 
175V 
350V 
Always keep your 
hands and metallic 
things away from 
the cabinet. 
DANGER! 
Don’t install 
the ground 
line 
Control Circuit 
Power source 
1¤, 240V, 50Hz 
Outdoor Electrical 
Indoor Electrical 
Compressor 
Motor 
(0V) 
ⓑ 
ⓐ 
P
ow
e
c
ir
c
ui
Across - (0V line)          approx 320~360V 
Across 
-ground                approx 155~170V 
Across 
 (0V line)-ground approx 155~170V 
Outdoor unit 
P.W.B. 
 
Always keep your 
hands and metallic 
things away from 
the oscilloscope 
DANGER! 
Don’t install 
the ground 
line 
Control Circuit