14.4.2  INDOOR FAN DOES NOT OPERATE (OTHERS ARE NORMAL) – RAK-25/35/50PXA, RAK-
18/25/35/50/70PPA, RAK-18/25/35/50PEA, RAF-25/35/50RPA, RAF-25/35/50PXA, RAD-50/60/70PPA 
Yes
Yes
Replace the fan motor
Replace the microcomputer
Can the fan be stopped 
by remote control?
Replace the microcomputer
The microcomputer fan PWM 
output at pin 
(24) is 1-5V
Perform final operation check
No
No
 
14.4.3  AIR DEFLECTOR DOES NOT MOVE (OTHERS ARE NORMAL) 
Yes
Yes
Are pulse signals output at 
microcomputer pin 
~⑱ when auto 
swing is turned ON in the fan mode?
Replace the microcomputer
No
No
Replace IC111
Is voltage over 15 or below 10V 
being generated on the 12V line?
Check IC711. If it is 
normal, replace the air 
deflector motor
Perform final operation check
 
 
14.4.4  CHECK THE CONTROL P.W.B. (POWER CIRCUIT) – RAK-25/35PXA, RAK-18/25/35PPA, RAK-
18/25/35/50PEA, RAF-25/35/50RPA, RAF-25/35PXA 
Yes
No
Is 35V or 20V being output at pinn⑤
relative to 0V at pin③ of CN3
Check to see if the connection cables 
are disconnected or reversed. If 
normal, check the outdoor unit P.W.B.
Is DC5V being 
generated?
Replace IC121. Check if a 
short occurs in the 5V 
line. If the 5V line is 
shorted, ICP1 will open 
again.
Is 12V or 7V being output 
at (+) relative to 0V at (-) 
of C114
Replace ICP1. Check if the air 
deflector motor is shorted 
and IC111, Q111, C114, ZD121 
are defective.
Is CP1 normal? Normal if 
it is less than 1
Ω . Blown 
(open) if it is 1
Ω or more.
Replace the terminal 
board. Insert the 
connection cable 
securely.
Has the terminal board 
thermal fuse blown 
(open)?
Replace Q111 and IC111
Perform final operation 
check
No
Yes
Yes (Normal)
Yes
(Open)
No
No
Yes
※2
1
 
1: When the unit is not in operation, the voltage across the 35V line may drop to 20V 
2: When the unit is not in operation, the voltage across the 12V line may drop to 7V