Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
14-27 
 
14.7.3 
MONO SPLIT INDOOR (RAK-18/25/35PSA, RAK-18/25/35PSAN, RAK-18/25/35PSPA)
 
No 
Blinking of TIMER lamp 
Reason for indication 
Possible causes 
 
When the indoor heat exchanger 
temperature is too low in the heating 
mode or it is too high in the cooling mode. 
Reversing valve defective 
1times 
1)  Reversing valve defective 
2)  Heat exchanger thermistor 
disconnected (only in heating mode) 
(Note) 
The malfunction mode is displayed only 
after  the abnormal condition occurrs 3
rd
 
time (read every 3 minutes 
 
 
When the outdoor unit is in forced 
operation or balancing operation after 
forced operation 
Outdoor unit is under forced operation. 
Electrical parts in the outdoor unit. 
 
 
When the interface signal from the 
outdoor unit is interrupted. 
Indoor/outdoor interface defective 
1)  Indoor interface circuit. 
2)  Outdoor interface circuit 
 
Malfunction of Power Relay  
Power Relay Defective 
 
 
When room thermistor or heat exchanger 
thermistor is opened circuit or short circuit. 
Room thermistor or heat exchanger 
thermistor is faulty 
1)  Room thermistor 
2)  Heat exhanger thermistor 
 
 
When over-current is detected at the DC 
fan motor of the indoor unit. 
Over-current detection at the DC fan 
motor 
10times 
1)  Indoor fan locked 
2)  Indoor fan  motor 
3)  Indoor control P.W.B. 
 
 
High Voltage Generator Defective 
 
 
1)    Connecting Cord Defective 
2)    Outdoor Defective 
 
When data read from IC401 or IC402 is 
incorrect. 
IC401 or IC402 data reading error 
IC401 or IC402 abnormal 
10 
 
 
Switch PWB Defective 
11 
 
 
Cleaning Unit Defective 
12 
 
 
Failure of Peltier Device 
*Note: Refer to Chapter 9 for error codes displayed on remote controllers. 
(
 Lights for 0.35 sec. at interval of 0.35 sec.) 
<Cautions> 
1)  If the interface circuit is faulty when power is supplied, the self diagnosis display will not be displayed 
2)  If the indoor unit does not operate at all, check if the connecting cable is connected to the outdoor unit. 
 
2sec 
1 time 
2sec 
2 times 
2sec 
3 times 
2sec 
9 times 
2sec 
10times 
2sec 
5 times 
2sec 
11times 
2sec 
12times 
2sec 
13times 
2sec 
17times 
2sec 
18times 
2sec 
19times