Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
14-32
 
 
14.8.2  MULTIZONE 
SELF-DIAGNOSIS LIGHTING MOD
  : LIGHT 
  : BLINK 
  : OFF 
L
D
3
0
L
D
3
0
L
D
3
0
L
D
3
0
SELF DIAGNOSIS NAME 
DETAIL 
MAIN CHECK POINT 
RED RED RED GRN 
 
 
 
1.  DURING OPERATION 
 
 
 
 
Normal Operation 
Compressor Operation 
Not Malfunction 
 
 
 
 
Overload (1) 
 
The rotation speed is automatically controlled to 
protect the compressor in the overload 
condition. 
This shows an overload but not malfunction. 
 
 
 
 
Overload (2) 
 
 
 
 
Overload (3) 
Example of blinking (5 times) 
 
2.  DURING STOP 
 
 
 
 
Abnormal Thermistor 
Thermistor is opened or shorted. 
Refer to the table below 
①Thermistor ②Connection of Thermistor 
is faulty ③Thermistor Circuit 
Lit 
1~11 
Times 
Blinking times 
Reference Table  for Abnormal Thermistor 
1 Times 
Overheat Thermsitor 
8 Times 
Narrow Pipe Thermistor (Indoor 3) 
2 Times 
Defrost Thermistor 
9 Times 
Wide Pipe Thermistor (Indoor 3) 
3 Times 
Outdoor Temperature Thermistor 
10 Times 
Narrow Pipe Thermistor (Indoor 4) 
4 Times 
Narrow Pipe Thermistor (Indoor 1) 
11 Times 
Wide Pipe Thermistor (Indoor 4) 
5 Times 
Wide Pipe Thermistor (Indoor 1) 
12 Times 
Narrow Pipe Thermistor (Indoor 5) 
6 Times 
Narrow Pipe Thermistor (Indoor 2) 
13 Times 
Wide Pipe Thermistor (Indoor 5) 
7 Times 
Wide Pipe Thermistor (Indoor 2) 
 
 
L
D
3
0
L
D
3
0
L
D
3
0
L
D
3
0
SELF DIAGNOSIS NAME 
DETAIL 
MAIN CHECK POINT 
RED RED RED GRN 
 
 
 
 
 
 
 
Normal Stop 
Indoor Thermostat OFF.  
Main Operation OFF 
Not Malfunction 
 
 
 
 
Reset STOP 
When stop with Power RESET 
(Normal  when power has been 
Switched ON) 
①P.W.B. (Power Circuit, HIC, ETC) 
1 Time 
 
 
 
 
Peak Current Cut 
Over Current is Detected 
①Compressor ②P.W.B. 
 
 
 
 
①System Power Module ②P.W.B. 
2 Times 
 
 
 
 
 
Abnormal Low Speed 
Rotation 
Position Detection Signal is not 
input during operation 
①System Power Module ②Compressor ③
P.W.B 
3 Times 
 
 
 
 
Switching Failure 
Fail to Switch from Initial Low 
Frequency Sync to Position 
Detection Signal 
①System Power Module ②Compressor ③
P.W.B 
4 Times 
 
 
 
 
Overload Lower Limit Cut 
Overload protection mechanism is 
requesting compressor to run at a 
speed lower than the minimum 
speed limit 
①Outdoor unit is exposed to direct sunlight or 
its airflow is blocked. 
②Fan motor              ③Main PWB 
④The Voltage is extremely LOW 
5 Times 
 
 
 
 
2SEC 
Lights for 0.25 sec at 
interval of 0.25 sec 
 
TIME 
(1) 
(2) 
(3) 
SET 
VALUE 
RO
T
AT
IO
SPEED