Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
14-41 
 
 
14.10 THERMISTOR 
 
14.10.1 NAME AND ROLE OF EACH THERMISTOR 
 
Name 
Connector no. 
Measuring point 
role 
OH thermistor 
CN5 
Compressor head 
If the temperature of the compressor rises 
abnormally (118
o
C), the compressor will be 
stopped. The temperature is used to decide 
the operation of the valve 
DEF thermistor 
CN6 
Heat exchanger 
The thermistor decide the defrost operation 
during heating combine the data of the 
outside temperature and its data 
Outdoor temperature 
thermistor 
CN7 
Outside temperature 
Outdoor temperature is used to decide the 
various operation of the air conditioner 
Electrical Expansion valve 
thermistor (narrow pipe 1) 
CN8 
Indoor unit (narrow pipe 1) 
The thermistors detect the temperature of the 
piping to the indoor units. The temperature 
are used to decide how much the expansion 
valve is opened 
Electrical Expansion valve 
thermistor (narrow pipe 2) 
Indoor unit (narrow pipe 2) 
Electrical Expansion valve 
thermistor (narrow pipe 3) * 
Indoor unit (narrow pipe 3) 
Electrical Expansion valve 
thermistor (narrow pipe 4) * 
Indoor unit (narrow pipe 4) 
Electrical Expansion valve 
thermistor (wide pipe 1) 
CN9 
Indoor unit (wide pipe 1) 
Electrical Expansion valve 
thermistor (wide pipe 2) 
Indoor unit (wide pipe 2) 
Electrical Expansion valve 
thermistor (wide pipe 3) * 
Indoor unit (wide pipe 3) 
Electrical Expansion valve 
thermistor (wide pipe 4) * 
Indoor unit (wide pipe 4) 
“*” Starmark is applicable to respective models only 
 
14.10.2 REFERENCE VALUE FOR THERMISTOR’S RESISTANCE AND TEMPERATURE 
 
 
Electrical expansion 
valve thermistor 
Temperature 
Resistance 
Microcomputer 
pin potential 
DEF thermistor 
-15
o
12.6k
Ω 
1.0V 
 0
o
6.1 k
Ω 
1.7V 
 25
o
2.2 k
Ω 
3.0V 
 50
 o
860 
Ω 
3.9V 
 75
o
400 
Ω 
4.4V 
Outdoor temperature 
thermistor 
-15
o
12.6k
Ω 
1.0V 
 0
o
6.1 k
Ω 
1.7V 
 15
o
3.2 k
Ω 
2.4V 
 30
 o
2 k
Ω 
3.1V 
OH thermistor 
 25
 o
33.9 k
Ω 
0.5V 
 50
 o
10.8 k
Ω 
1.3V 
 75
 o
4.1 k
Ω 
2.4V 
100
 o
1.7 k
Ω 
3.4V 
105
 o
1.5 k
Ω 
3.6V 
118
 o
1 k
Ω 
3.9V 
 
NOTE: 
The table shows the corresponding reference value between thermistor’s resistance and the temperature. The value stated in the 
table might be slightly differ from measured value, depending on the measuring instrument. 
When measuring the resistance, pull out the connector after turning off the power supply to avoid voltage leak. 
WARNING: 
Pulling out the connector while the power supply is turn on will cause electrical shock, leak of current or burn of measuring 
instrument.