15.2.5.  AS TO PROPER DRAINAGE OF 
DEFROSTING WATER 
• 
At cold districts, there is a possibility that drainage 
can not be done due to freezing the defrosting 
water on the base surface. Therefore, please 
remove the drain pipes attached to the bottom of 
the outdoor unit and the bushes. If any, install at 
places where the defrosting water can flow 
smoothly. 
• 
The drainage holes will be covered by icicles 
which produced by the defrosting water from the 
bottom. Therefore please mount the unit at least 
250mm from the eaves and so on. 
To  make better drainage from bottom face of the 
outdoor unit 
 
CAUTION: 
– 
Drainage of the defrosting water by connecting the 
drain pipe will cause freezing. Do not do it. 
– 
If the bushes are not removed, the defrosting water will 
be  frozen at the base of the heat exchanger. This 
causes heating capacity to drop and abnormal noise 
operation. 
– 
If the blocks of the plastic block racks are used, the 
drainage hole at the base bottom may be blocked or 
covered with icicles (frozen water from defrost). Do not 
do it. 
Ensure enough clearance at the ground when installing 
the unit so the water could drain out smoothly. 
 
15.2.6.  REQUEST TO CUT NET ATTACHED TO 
REAR SIDE OF OUTDOOR UNIT 
At the places, where snow enters into the air inlet, the net 
at the rear side will lead to easy snow accumulation. 
Moreover, only the snow around the heat exchanger may 
be melted during defrosting whereas snow that attached to 
the net will remain stuck and not melt. Therefore, please 
cut the net at the rear after installation. 
 
15.2.7.  INSTALLATION OF HOT PIPE 
At places where the temperature is low, water from 
defrost can freeze easily and is impossible to drain out from 
the base bottom.  The Hot-pipe is to be used so that the 
drainage holes will not be blocked. 
NOTE: 
– 
No responsibility is accepted for any form of use other 
than the designated applications. 
– 
Heating and cooling capability may be slightly affected 
by the use of the hot pipe. 
– 
Time taken to heat and cool may be slightly longer 
when the hot pipe is used. 
 
1.  Turn off the circuit breaker and remove the connecting 
cord.  
2.  Remove the attached pipes from the service valve. 
3.  Remove external parts as show in below figure. 
 
Service valve for small diameter 
side of outdoor unit 
Small diameter 
pipe 
Hot pipe 
The defrosting 
water should be 
drained out as 
soon as 
possible 
At least 
250mm from 
ground level 
Please remove the drain 
pipes/bushes completely 
Although installed 
on the wall, drain 
holes will still be 
blocked by icicles 
when water could 
not be drained out 
properly  caused by 
insufficient 
clearance at the 
bottom base. 
 
Installation using 
high position racks 
Installation using 
metal fittings on wall 
Net 
Outdoor 
unit side 
heat 
exchange
 
Base of 
outdoor 
unit 
Net 
Enlarged figure of 
this portion 
Outdoor 
temperature 
thermistor 
Cut off position 
As the upper drawing, please cut off 
and remove the lower part of the net.