Hitachi RAF-35RPA RAF35RPA User Manual

Product codes
RAF35RPA
Page of 706
 
15-9 
 
iii)  Install the electrical box cover paying 
attention not to clamp the cable. Read the 
installation manual of each room air-
conditioner for confirming how to connect and 
how to assemble the cable of the RAC 
adaptor. 
CAUTION: 
– 
Disconnect the power plug before performing this work 
– 
Turn OFF the break power source in case the power is 
supplied from the outdoor unit. 
• 
Connection of Transmission Cable 
H-LINK transmission cable connecting to RAC adaptor 
shall be connected to H-LINK. 
 
CAUTION: 
– 
DO NOT connect incorrect wiring. It may cause the 
failure of the RAC Adaptor. Especially pay attention 
not to apply high voltage e.g. AC400/230V. 
– 
DO NOT perform the wiring work while power to the 
central station or the RAC Adaptor is still being 
supplied.. It may cause malfunction. Turn OFF devices 
when performing the wiring work. 
– 
The RAC Adaptor side cable should not overload to 
the connector. 
– 
DO NOT clamp the cable when attaching the RAC 
adaptor cover. 
– 
Band should not be loose and in fixed position. 
15.3.4.  DIP SWITCH SETTING 
1)  Switch OFF the power of room air conditioner before 
setting the DIP switch. If the power is ON, the settings 
are INVALID. 
2)  The position of the DIP switch is shown below. 
 
CAUTION: 
– 
DO NOT turn ON various pins of DSW1 and DSW2 
3)  Set the refrigerant cycle# by RSW1 and DSW1 
DSW1 (Ten digit) 
RSW1 (Last digit) 
 
 
DSW1 and RSW1 are set “0” before shipment. Up to 15 
cycles can be set. 
E.g. Setting in Ref No. 5 
 
 
4)  Set the unit No. by RSW2 and DSW2 
DSW2 (Ten digit) 
RSW2 (Last digit) 
 
 
DSW2 and RSW3 are set “0” before shipment. Up to 15 
cycles can be set. 
E.g. Setting in Unit No. 15 
 
 
 
5)  Slave unit. 
In case of setting various RAC adaptors in the same 
refrigerant cycle, set the RAC adaptor with smallest 
Unit# as a master unit. In case of setting only one RAC 
adaptor in a refrigerant system, this adaptor should be 
a master unit. Set this procedure by DSW3. 
Master Unit setting 
Setting before shipping 
(slave unit setting) 
 
 
: Master Unit setting 
: Setting before Shipping (Slave Unit setting) 
Use enclosed 
connector 
Connector 
(Accessory) 
RAC Adaptor 
H-LINK wiring 
To other 
connection 
device of H-LINK 
Fixed position 
Band 
PCB 
RSW1 (Refrigerant 
cycle# setting 
RSW1 
Unit# setting 
DSW1 (Refrigerant 
cycle# setting) 
DSW2 (Unit# 
setting) 
LED 
H-LINK 
transmission 
DSW3  
Unit# setting 
LED 
DSW4  
(Fuse recovery 
and terminal 
resistance 
setting 
ON 
OFF 
Position 
Turn by using 
a screw driver 
ON 
OFF 
No. 1 pin is OFF 
RSW1 
The position is Set 5 
ON 
OFF 
Position 
Turn by using a 
screw driver 
ON 
OFF 
No. 1 pin is OFF 
RSW2 
The position is Set 5 
ON 
 
ON