MISCELLANEOUS NOTE
 
15-10
 
 
 
CAUTION: 
– 
DO NOT set various main adaptors in the same 
refrigerant cycle. 
6)  Procedure when applying 200V voltage to H-LINK 
wiring incorrectly. 
In case of applying 200V voltage to H-LINK wiring 
incorrectly, the fuse installed in a transmission circuit 
on PCB will blow out. In this case, reconnect the wiring 
correctly and turn ON No. 2 pin of DSW4 on PCB. The 
transmission circuit can be recovered. (If applying this 
error again, the transmission circuit can not be 
recovered) 
 
7)  Terminating resistance is set in whole H-LINK system. 
a)  If H-LINK connecting devices like package air-
conditioner  are  connected besides the RAC 
Adaptor, set the terminating resistance by those 
connecting devices. The  terminating resistance 
should be set ON in only one position in whole H-
LINK system. 
b)  In case that H-LINK is connected only by the RAC 
adaptor, set the terminating resistance by the 
RAC adaptor. The terminating resistance should 
be set ON in only one position in whole H-LINK 
system. 
 
15.3.5.  TEST RUN 
Test run should be performed in the following after finishing 
the installation, wiring and setting. Refer to the installation 
manuals enclosed with the control system equipment. 
1)  Confirmation of RAC Adaptor Connection 
Confirm if the RAC adaptor connection is recognized in 
the control system equipments. In case that it is not 
confirmed, check the transmission cable, refrigerant 
cycle #, indoor unit #, terminal resistance setting etc. 
2)  Registration 
Confirm if the RAC adaptor connection is recognized. 
3)  Confirmation of RUN/STOP Operation. 
Confirm if the room air-conditioner operate correctly by 
RUN/STOP from the central control system 
equipments. Check also if the room air-conditioner 
operation changes correctly by each setting. 
 
 
Refrigerant 
Unit# 
Indoor Unit# 
DSW4 
Turn ON No.2 pin of 
DSW4 
ON
 
PCB 
DSW4 
Turn ON No.1 pin of 
DSW4 
ON
 
PCB