Eaton Sola 26 2605-1000M User Manual
Product codes
2605-1000M
2
ORDERING DETAILS
240 VOLT IN/OUT
Rated
Rated
Current
Enclosure
Output Part AMPS Output Weight Size
VA
VA
Number
(Cont.) Receptacles
(kg)
(Note 3)
500 210-26-650-00 2.08
2
23
3
1000 210-26-710-00 4.16
3
36
4
2000 210-26-720-00 8.33
3
55
4
2500 210-26-725-00* 10.41
3
66
4
220 VOLT IN/OUT HARDWIRED UNITS
Rated
Rated
Current
Enclosure
Output Part AMPS
Weight Size
VA
Number
(Cont.)
(kg)
(Note 3)
500 200-44-650 2.27
23 3
1000 200-44-710 4.55
36 4
2000 200-44-720 9.09
55 4
2500 200-44-725 11.36
66 4
INPUT
Voltage:
Voltage:
220 or 240 Volt AC
Frequency:
50 Hz
Input Voltage Range:
+ 10%, -20% (±40%)
Protection:
ANSI/IEEE C62.41-1980
A and B waveforms suppressed
to safe levels.
OUTPUT
Nominal Voltage:
Nominal Voltage:
220 or 240 Volt AC
Frequency:
50 Hz
Voltage Regulation:
±3% for +10%, -20% input.
+5%, -8% for ±40% input.
Control:
AC on/off switch
Power Efficiency:
90%
Response/Correction
Return to regulation envelope within
Time:
30 msec.
Dynamic Response:
Continuous and smooth correction
for input voltage fluctuations.
OVERLOADS
200% of rated load for 10 seconds
without damage. 500% of rated load for
10 msec.
ELECTRICAL NOISE ATTENUATION
Transverse Mode:
Transverse Mode:
60 dB typical, (80 dB max.)
4kHz to 20 MHz
Common Mode:
120 dB typical, (140 dB max.)
2kHz to 1 MHz
2kHz to 1 MHz
OUTPUT HARMONIC
Less than 3% THD on linear loads.
DISTORTION
No greater than 5% on typical
computer loads.
computer loads.
ENVIRONMENTAL
Operating Ambient:
Operating Ambient:
-20ºC to +50ºC
Relative Humidity:
0 to 95% non-condensing
Ventilation:
Natural Convection Cooled
STATUS INDICATION
Power On:
Power On:
Amber lamp
OVERLOAD PROTECTION Output short circuit protection
WARRANTY
5 years
Sola 200/210
Notes:
1. 240 Volt Hardwired options available to order
2. Special voltage configurations available to order
3. Enclosure sizes (mm) Size 3: 195 (H) x 210 (W) x 328 (D)
1. 240 Volt Hardwired options available to order
2. Special voltage configurations available to order
3. Enclosure sizes (mm) Size 3: 195 (H) x 210 (W) x 328 (D)
Size 4: 252 (H) x 280 (W) x 421 (D)
4. * Input lead fitted with 15 Amp plug top (all other units fitted with
10 Amp plug tops)
5. Specific input leads and output sockets can be fitted to order
Designed and manufactured in Australia, the Sola
200/210 portable power conditioner provides smooth
stepless control of output voltage to your computer or
electronic system, whilst attenuating harmful impulses,
surges and other power line disturbances.
The Sola 200/210 incorporates improved surge withstand
capabilities, as specified by ANSI/IEEE C62.41-1980 and
is covered by the SECV Certificate of Suitability Number
CS84292V.
Built to protect
• Programmable logical controls (PLC)
• Photographic equipment
• Remote computer peripherals
• Copiers and laser printers
• Process control equipment
• CNC machinery
• Entire installations
500VA to 2500VA Portable Power Conditioners
Specifications