The extension of Sola ferroresonant power conditioners 
continues through to 22kVA. These units are mostly suited to 
hardwired, fixed installation applications for providing smooth 
stepless control of the output voltage, attenuation of harmful 
impulses or surges and other power line disturbances. Sola 
200 power conditioners are ideally suited to provide protection 
in computer rooms, regulation for scientific instrumentation, 
plus protection and regulated power to sophisticated computer 
based factory process equipment. To simplify installation, 
all units are free standing and fitted with castors (excluding 
22kVA) and jacking feet. Connections are provided at the rear 
via a base plate cable entry to an isolation switch.
The flexibility of Sola 200 power conditioners is increased on 
units between 7.5kVA and 18kVA. These units can be field 
configured for single phase or three phase operation. Sola 200 
power conditioners (3 to 22kVA) incorporate approved surge 
withstand capabilities, as required by ANSI/IEEE C62.41-1980.
Built to protect: Remote computer peripherals
Copiers and laser printers, Process control equipment, 
CNC machinery, Programmable logical controls (PLC), 
Photographic equipment
, entire installations.
SPECIFICATIONS
INPUT
Voltage: 
 220 or 240 Volt AC (Refer “Ordering Details” for 
configuration options)
Frequency: 
50 Hz
Input Voltage Range: 
+ 10%, -20% (±40%)
Protection: 
ANSI/IEEE C62.41-1980 
 
A and B waveforms suppressed  
 
to safe levels.
OUTPUT
Nominal Voltage: 
220 or 240 Volt AC
Frequency: 
50 Hz
Voltage Regulation: 
±3% for +10%, -20%  input.  
 
+5%, -8% for ±40% input.
Control: 
AC on/off switch
Power Efficiency:                          90%
Response/Correction Time: 
Return to regulation envelope within  
 
30 msec.
Dynamic Response: 
Continuous and smooth correction  
 
for input voltage fluctuations.
OVERLOADS
 
 200% of rated load for 10 seconds without 
damage. 500% of rated load for 10 msec.
ELECTRICAL NOISE ATTENUATION
Transverse Mode: 
60 dB typical, (80 dB max.)  
 
4kHz to 20 MHz
Common Mode: 
 120 dB typical, (140 dB max.)  
2kHz to 1 MHz
OUTPUT HARMONIC 
Less than 3% THD on linear loads.  
DISTORTION 
 No greater than 5% on typical  
computer loads.
ENVIRONMENTAL
Operating Ambient: 
-20ºC to +50ºC
Relative Humidity: 
0 to 95% non-condensing
Ventilation: 
Natural Convection Cooled
STATUS INDICATION
Power On: 
Amber lamp
OVERLOAD PROTECTION 
Output short circuit protection
WARRANTY 
5 years
ORDERING DETAILS
Rated  
 
 
Enclosure 
Output  *Part 
 
Weight Size
kVA 
Number 
Configuration 
(kg) 
(Note 5)
200-26-730 
1 Phase only 
100 
1
200-26-730-00** 
1 Phase only 
100 
1
200-26-750 
1 Phase only 
155 
2
200-26-750-HO*** 
1 Phase only 
155 
2
7.5 
200-26-775**** 
1 or 3 Phase 
215 
2
200-26-790**** 
1 or 3 Phase 
270 
2
12 
200-26-812M**** 
1 or 3 Phase 
360 
3
15 
200-26-815**** 
1 or 3 Phase 
420 
3
18 
200-26-818**** 
1 or 3 Phase 
520 
3
22.5 
200-46-822**** 
3 Phase only 
595 
4
Notes:
1.   *  For units with nominal input/output voltage of 220 specify -44-, as in 
200-44-730
2.   **  Units fitted with WIP 15 plug and 4 x 10/15 Amp screw sockets
3.   ***  Units fitted with input terminal block and 4 x 10/15 amp screw 
sockets
4.   To avoid nuisance tripping of input circuit breakers, we recommend 
the use of "D" curve or motor start type circuit breakers. Current rating 
should be at least one size larger than input current stated on unit  
data plate. See manual or consult your sales representative for  
further details.
5.  Enclosure Sizes (mm):   Size 1: 600 (H) x 400 (W) x 440 (D)
   
 
           Size 2: 995 (H) x 525 (W) x 550 (D)
   
 
           Size 3: 990 (H) x 800 (W) x 550 (D)
   
 
           Size 4: 1236 (H) x 800 (W) x 550 (D)
6.   ****  3 Phase loads to be star connected only. Power Conditioners NOT 
to be used for Delta loads.
3kVA to 22kVA Power Conditioners
Sola 200
  Specifications
  Ordering details