Acer E3-1220 v3 KC.12201.3E3 User Manual

Product codes
KC.12201.3E3
Page of 116
The Ψ
CA
 point at DTS = -1 defines the minimum Ψ
CA
 required at TDP considering the
worst case system design T
AMBIENT
 design point:
Ψ
CA
 = (T
CASE-MAX
 – T
AMBIENT-TARGET
) / TDP
For example, for a 95 W TDP part, the T
case
 maximum is 72.6 °C and at a worst case
design point of 40 °C local ambient this will result in:
Ψ
CA
 = (72.6 – 40) / 95 = 0.34 °C/W
Similarly for a system with a design target of 45 °C ambient, the Ψ
CA
 at DTS = -1
needed will be 0.29 °C/W.
The second point defines the thermal solution performance (Ψ
CA
) at T
CONTROL
. The
following table lists the required Ψ
CA
 for the various TDP processors.
These two points define the operational limits for the processor for DTS 1.1
implementation. At T
CONTROL
 the fan speed must be programmed such that the
resulting Ψ
CA
 is better than or equivalent to the required Ψ
CA
 listed in the following
table. Similarly, the fan speed should be set at DTS = -1 such that the thermal
solution performance is better than or equivalent to the Ψ
CA
 requirements at T
AMBIENT-
MAX
. The fan speed controller must linearly ramp the fan speed from processor DTS =
T
CONTROL
 to processor DTS = -1.
Figure 16.
Digital Thermal Sensor (DTS) 1.1 Definition Points
Thermal Management—Processor
Intel
®
 Xeon
®
 Processor E3-1200 v3 Product Family
June 2013
Datasheet – Volume 1 of 2
Order No.: 328907-001
65